during a start shall only be added to the list if the motor start fully completes the start (i.e. the starter reaches
up to speed).
z
NOTE:
This feature should not be used on systems where the starting load varies greatly from start to
start.
See Also
Motor OL Lockout Level (PFN 34) on page 89.
Theory of Operation 7.1, Solid State Motor Overload Protection on page 114.
Jump to Parameter
I/O 00
LCD Display
Description
By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter
within that group.
Digital Input Configuration
I/O 01 - I/O 08
LCD Display
Range
LCD
Description
Off
Off, Not Assigned, Input has no function.
(Default DI02 -DI08)
Stop
Stop Command for 3-wire control.
(Default DI 1)
Fault High
Fault High, Fault when input is asserted, 120V applied. See (I/O 09) on page 91.
Fault Low
Fault Low, Fault when input is de-asserted, 0V applied. See (I/O 09) on page 91.
Fault Reset
Reset when input asserted, 120V applied.
Disconnect
Disconnect switch monitor.
Inline Cnfrm
Inline contactor feedback.
Bypass Cnfrm
Bypass/2M, bypass contactor feedback, 2M contactor feedback in
full voltage or Wye-delta.
E OL Reset
Emergency Motor Overload content reset. After an OL trip has
occurred. Reset when input asserted, 120V applied.
Local/Remote
Local/Remote control source, Selects whether the Local Source
parameter or the Remote Source parameter is the control source.
Local Source is selected when input is de-asserted, 0V applied.
Remote Source selected when input asserted, 120V applied.
Heat Disable
Heater disabled when input asserted, 120V applied.
Heat Enable
Heater enabled when input asserted, 120V applied.
Ramp Select
Ramp 2 is enabled when input asserted, 120V applied.
Slow Spd Fwd
Operate starter in slow speed forward mode.
Slow Spd Rev
Operate starter in slow speed reverse mode.
Brake Disabl
Disable DC injection braking.
Brake Enabl
Enable DC injection braking.
Speed Sw NO
Speed Switch Normally Open, 0V applied. See (PFN 26) on page 85.
Speed Sw NC
Speed Switch Normally Closed, 120V applied. See (PFN 26) on page 85.
Description
I/O 01-03 parameters configure which features are performed by the DI 01 to DI 03 terminals.
I/O 04-08 parameters configure which features are performed by the DI 04 to DI 08 terminals.
90
6 - PARAMETER DESCRIPTION
I/O: DI 5 Config
05
Off
I/O: DI 6 Config
06
Off
I/O: DI 8 Config
08
Off
I/O: DI 7 Config
07
Off
I/O: DI 2 Config
02
Off
I/O: DI 3 Config
03
Off
I/O: DI 4 Config
04
Off
I/O: Jump Code
00
1
I/O: DI 1 Config
01
Stop
Содержание RediStart EXEXMVRMX3 Series
Страница 2: ......
Страница 10: ......
Страница 11: ...1 Introduction 1...
Страница 17: ...2 Technical Specifications 7...
Страница 27: ...3 Installation 17...
Страница 38: ...EXMVRMX3 I O Card Layout 3 9 EXMVRMX3 I O Card Layout 28 3 INSTALLATION Figure 11 EXMVRMX3 I O Card Layout...
Страница 48: ......
Страница 49: ...4 Keypad Operation 39...
Страница 59: ...5 Parameter Groups 49...
Страница 67: ...6 Parameter Description 57...
Страница 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Страница 123: ...7 Theory of Operation 113...
Страница 155: ...NOTES 145 7 THEORY OF OPERATION...
Страница 156: ...146 7 THEORY OF OPERATION...
Страница 157: ...8 Troubleshooting Maintenance 147...
Страница 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Страница 186: ......
Страница 187: ...Appendices 177...
Страница 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Страница 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...