Reference Manual
BLR-CX-R / BLR-CX-T
Rev. 07
2018-07
28
515
Control alarm (target cos φ can not be archived)
Yes/No
"YES" alarm is triggered after 75 time switching time with
▲
Q>
smallest step (Over / under compensation). Controller opens the
alarm contact and indicates
in the Display.
"NO" no monitoring for over / under compensation.
516
Defective step alarm
Yes/No
"YES" After 3 unsuccessful switching actions alarm is triggered. The
controller opens the alarm contact and indicates
/
in the display.
Steps recognized as defective flashing in the step indication.
"NO" alarm disabled.
517
Step power loss alarm
Yes/No
"YES" If the current step size is less than 70% of the initial size, the
controller opens the alarm contact and indicates the error with
output number
/
. in the display.
"NO" Power loss of the capacitors is not monitored.
6.6
600 Resetmenu
Allows you to reset all settings made by the controller and stored data. Additionally, it
contains the software version of the device (displayed from 1.04).
600
Resetmenu
MENU FUNCTION
RANGE
601
Reset Settings
Yes/No
Sets all settings made back to factory settings.
602
Reset Step database
Yes/No
Sets all step data back to factory settings.
603
Reset operation hours
Yes/No
Sets the counter for operation hours to "0"
604
Reset average PF
Yes/No
Reset the average PF.
605
Reset max. Temperature
Yes/No
Reset the highest measured Temperature.
606
Reset alarms
Yes/No
Reset all upcoming alarm.