Reference Manual
BLR-CX-R / BLR-CX-T
Rev. 07
2018-07
9
In case of an alarm will flash alternately at BLR-CX with "ALARM" an error code in the display.
The table below gives an overview of all possible error codes.
To reset pending alarms hold the
(esc) button pressed for 5 seconds.
measured voltage is outside the set tolerance
measured current is less than 15mA (check the short
circuit bridge K and L and the entire current path
measured current is to high
The controller cannot achieve the target COS φ
The set limit for the THD of the voltage is exceeded
/
One or more steps are broken. The defective step is
blinking with the alarm message.
/
One or more step's have fallen below 70% of initial
power. step number and error code will flash alternately.
For devices with software version before 1.04 the alarm
is triggered at 50% of initial power.
The second temperature limit is exceeded. Stage were
switched off successively.
Set limit of operation hours has been exceeded
/
Set limit of the max. allowable operation cycles, for one
or more steps, has been exceeded.
/
Abort of auto-initialization.