9
APPLICATIONS
9.1
Fan Control
The fan control is to be regulated through the BLR-CX.
Solution:
If the BLR-CX is equipped with a temperature sensor (option –L), can be via one of the
switching exits, a fan to be controlled.
Procedure:
Enable temperature alarm
In the expert menu item 512 set to "YES" (temperature alarm on).
Set temperature thresholds
Set the following items 513 (temperature threshold 1) and 514 (temperature threshold
2the temperature thresholds. By exceeding the temperature threshold 1 is witched the
fan output. When you exceed the temperature threshold 2, all steps are switched off to
prevent overheating.
Select fan output
Select item 403 in expert menu and adjust for the step which shall work as the fan output
step type "AL".
Features:
In order to prevent hunting of the fan relay, the fan is turned off only at a temperature below
the set limit by at least 3°C. If the BLR-CX is equipped with a temperature sensor, the current
cabinet temperature is displayed and the highest measured temperature is stored in thi.
Parallel to the temperature sensor can be connected a thermostat. By close of the thermostat,
the temperature limit 2 is activated.