Reference Manual
BLR-CX-R / BLR-CX-T
Rev. 07
2018-07
12
5.2
Info (Step database)
In the "INFO" menu for each connected step the number of switching cycles, the current step
size and the step size in relation to the initial step size is stored.
Using these data, conclusions can be drawn on the condition of the site and the condition of
single steps. Step sizes are displayed in kVar only when in the CT ratio is set in "Setup" menu.
1.00
i
Choose step with
Confirm with
View values with
1.00
i
INFO
INFO
CC
25
kVar
Display of step size only if
CT ratio is set, otherwise---
1 2 3 3 4 max.
1
2
3
4
max.
1.00
i MANUAL
INFO
98
%
Current step size in %
related to initial step size
1 2
3
4
max.
1
2
3
4
max.
1.00
i SETUP
INFO
OC
808
switch cycles
1
2
3
4
max.
1
2
3
4
max.
Auto
auto: step is okay
foff: step is permanent off
fon: step is permanent on
Al: output for fan control
Flty: step detected as
faulty
1
2
3
4
max.
INFO
CC
25
kVar
Display of step size only if
CT ratio is set, otherwise---
1
2
3
4
max.
1
2
3
4
max.
Auto
auto: step is okay
foff: step is permanent off
fon: step is permanent on
Al: output for fan control
Flty: step detected as
faulty
1
2
3
4
max.