PHASE COMPENSATION
0...345
The phase compensation enables the user to connect the current-
and voltage measurement channels in any way. This compensation
angle complies with the phase angle between connected active
current and voltage. This setting has to be made correct, because
otherwise correct regulation is not possible! If the current
transformer is connected inverted, additionally a phase
compensation of 180° has to be respected.
Is auto-initialization failed due to adverse network conditions, by
hand a correction angle can be set or the incorrectly recognized can
be corrected. Table 11.1 gives an overview of the connection options
with corresponding phase angles.
207
START AUTO-INITIALIZING
Yes/No
"YES" starts auto-initializing
Automatic initialization is switching all exits. During this test it can
get information, which exits are working and it can correct the
connection of the measuring channels for voltage and current by
internal
settings.
Automatic initialization can be started only when the voltage and
current are ok.
AUTOMATIC INITIALIZATION is only able to work, when capacitors
are used for compensation. If BLR-CX has to switch reactors for
compensation of capacitive load, this feature will cause failures. AI
is working at best, when there are stable load conditions!
Steps with step type "FON" or "AL" will be not considered in case of
new auto-initialization.
At devices with software revision before 1.04, stages which are set
to "FOFF" were not retested.
208
AUTO-INITIALIZING BY REGULATOR RESTART
Yes/No
YES = after starting the BLR-CX, a countdown is running. During this
countdown it is possible to start auto-initializing by
pushing
(
).
"NO" the countdown is not shown. To start AI, you have to choose
Quickstart SETUP.