background image

Technical Manual 

 

 

LioN-Link PROFINET 

 

Subject to change without notice! 

 

Version 1.2 / August 2014 

 

 

Page 7 of 30 

 
 

2.

 

System description 

 

LioN (Lumberg i/o network)-Link is a modular system for the decentralized operation in rough industrial environment for the 
simple handling of the I/O data in a superordinate bus system. It is particularly suitable for application places with high I/O 
concentration on distributed assemblies. 
 
By the very compact dimensions and the low weight the system can be used under limited space conditions and on handling 
devices. As a protection class LioN-Link offers IP 67. 
 
The LioN-Link system consists of the BusHead - the connection to the superordinate field bus - and the different field-bus-
independent I/O modules. The maximum expansion of the link system amounts to 100 m for each link connection (two 
connections for each BusHead => total extension 200 m). 
 
Each line can be extended with up to 15 I/O modules. The distance between two link participants is arbitrary. The permissible 
overall length for each line may not be exceeded however. Using the maximum expansion of the system an additional feed of 
the power supply for the system and sensors is possible through T-connectors and/or at the last link participant. 
 
In order to keep the permissible values for a safe power supply of the modules it is necessary to calculate each system under 
the actual conditions (number of the modules and sensors as well as the cable length between the modules). For this a 
calculation table is available at the link 
 

http://www.beldensolutions.com/en/Service/Downloadcenter/Software_Lumberg/index.phtml

 

 
An example can be found in this manual in chapter 5.2.2. 
 
As a link cable we recommend a standard CAN/DeviceNet cable. Also unshielded 5-pole cables with standard M12 plugs and 
jacks are suitable. As an alternative also Fixcon plugs and jacks can be used. 
 
With the use of an unshielded cable an extension of 25 m for each line connection should not be exceeded. In plants with EMC 
load (in the near of controlled motors, frequency converter drives or in welding applications) the use of shielded cables 
(standard CAN/DeviceNet) is necessary. 

Содержание Lumberg Automation 0970 ESL 601

Страница 1: ...Technical Manual 0940 ESL 601...

Страница 2: ...pole D coded 12 5 1 2 Power supply connector for the BusHead M12 plug 5 pole 12 5 1 3 Link system connector M12 socket 5 pole 13 5 2 Intermediate power supply feed on LioN Link I O modules 14 5 2 1 T...

Страница 3: ...7 3 The monitoring page Monitoring 25 8 Firmware update 26 9 Alarm and error messages of the BusHead 27 9 1 Evaluation of alarms in STEP7 27 9 1 Reaction of the BusHead to a module breakdown pull ala...

Страница 4: ...s please do not hesitate to contact us We will be glad to be at your disposal at any time Belden Deutschland GmbH Lumberg Automation Im Gewerbepark 2 58579 Schalksmuehle Germany Tel 49 0 23 55 5044 00...

Страница 5: ...ferences in the residential area In this case the operator can be required to accomplish appropriate measures The proper and safe function of the product requires an appropriate transport storage inst...

Страница 6: ...ledge of the relevant standards have the same level of knowledge as after a technical education due to an activity in a comparable area for several years Modifications to the hard and software of our...

Страница 7: ...s is arbitrary The permissible overall length for each line may not be exceeded however Using the maximum expansion of the system an additional feed of the power supply for the system and sensors is p...

Страница 8: ...pole interface M LioN Link special modules 0942 UEM 620 IO Link master 4xM12 S 0942 UEM 783 Motion drive control 8xM12 M 3 3 Accessories Part number Description PROFINET 0985 342 100 M Connecting cabl...

Страница 9: ...ocket straight 5 pole contacts 1 3 connected A coded Field attachables 0986 EMC 102 Field attachable M12 plug for PROFINET cable straight 4 pole D coded with spring type terminals RSC 5 9 Field attach...

Страница 10: ...Technical Manual LioN Link PROFINET Subject to change without notice Version 1 2 August 2014 Page 10 of 30 4 Mounting 4 1 Outer dimensions...

Страница 11: ...g a flat washer according to DIN 125 has to be used Important note For the derivation of interference currents and or for the EMC stability the module provides a metal grounding sheet It is necessary...

Страница 12: ...lines 24 V DC to the data lines 5 1 2 Power supply connector for the BusHead M12 plug 5 pole Colour code of the connector grey Connector Pin Signal Function PROFINET ports P1 P2 1 TD Transmit Data 2 R...

Страница 13: ...in 4 Data Pin 5 Also the reverse connection of the power supply lines can lead to the destruction of the module Important note With long cable lengths an additional power supply feed is recommended se...

Страница 14: ...ctronics and sensors of the I O modules can be necessary If the power supply for the I O modules is not sufficient they deliver a diagnostics message The warning threshold for the diagnostics is appro...

Страница 15: ...ink line a calculation table as a Microsoft Excel sheet is available under http www beldensolutions com en Service Downloadcenter Software_Lumberg index phtml The table determines the voltage drop on...

Страница 16: ...g index phtml On request the GSDML file is also mailed by the support team The name of the file is as follows GSDML v2 2 Lumberg Automation LioN Link yyyymmdd xml in which yyyymmdd expresses the relea...

Страница 17: ...SL601 in the hardware catalogue Move the system to the PROFINET line of the control unit Insert now the I O modules of the LioN link system connected to the BusHead into the configuration Locate the I...

Страница 18: ...g and choose the menu item Edit Object Properties In the opening dialogue window you can change the device name Check whether the displayed IP address is correct and control unit and BusHead are locat...

Страница 19: ...ps determined by the IO Devices The LioN Link PROFINET BusHead supports the function of device exchange without removable media PG The topology of the network has to be configured for the use of the f...

Страница 20: ...Technical Manual LioN Link PROFINET Subject to change without notice Version 1 2 August 2014 Page 20 of 30...

Страница 21: ...missioning it is recommended to leave the parameter Interchanged Modules on the setting ACCEPT default setting In this mode it is possible to find the optimal installation and the most favourable wiri...

Страница 22: ...box Prioritized Start up in the window Properties Interface X1 should not be selected 6 4 6 Resetting the BusHead to factory settings In STEP7 resetting the BusHead to factory settings is carried out...

Страница 23: ...IP address According to the PROFINET standard all PROFINET IO devices are delivered with IP address 0 0 0 0 This means a free IP address deviating from the factory settings has to be assigned to the...

Страница 24: ...nfiguration page Configuration With the selection of the menu item Configuration on the left side of the homepage you are requested to enter a user name and a password Enter Admin as the user name and...

Страница 25: ...is also possible on this side The procedure is described in one of the following chapters of this manual and should be absolutely observed 7 3 The monitoring page Monitoring The page Monitoring gives...

Страница 26: ...s 0940ESL601_ERTEC bin The file names may not be changed 6 By clicking on the button Apply the firmware file is transferred to the BusHead Due to the size of the firmware for the ERTEC chip this proce...

Страница 27: ...iled information about the fault can be obtained in the fault OB by calling the SFB 54 RALRM Receive additional alarm information The SFB 54 therefore has to be called in every fault OB If the called...

Страница 28: ...xF Number of module with diagnostics Error code 0x00 Reserved 0x01 Short circuit 0x02 Low voltage 0x03 Overvoltage 0x04 Overload 0x05 Over temperature 0x06 Broken wire 0x07 Upper limit value exceeded...

Страница 29: ...ASE TX supported Manufacturer code Vendor ID 0016AH Device code Device ID 0302H Supported Ethernet protocols Ping ARP LLDP SNMP Network diagnostics DCP HTTP TCP IP Switch functionality integrated IRT...

Страница 30: ...th I O modules red Incorrect configuration modules permuted red green alternating flashing Restart of line 1 and or line 2 off Line 1 and or line 2 not used no I O module connected P1 Lnk Act P2 Lnk A...