6.4.
Configuration of the LioN-Link PROFINET system in
STEP7
After the installation of the GSDML file for the BusHead the LioN-Link system is available in the hardware catalogue under
PROFINET IO – Additional Field Devices - I/O - Lumberg LioN-Link
.
First configure the control system in the usual way. Assign an IP-address and a subnet mask for the PROFINET port of the
control unit.
Afterwards click on the part description of the BusHead
0940ESL601
in the hardware catalogue
.
Move the system to the
PROFINET line of the control unit.
Insert now the I/O modules of the LioN link system connected to the BusHead into the configuration.
Locate the I/O-modules connected to line 1 to the slots 1 to 15. The slots 16 to 30 are to be filled with the I/O-modules of the
second line. It is allowed to leave slots free, placeholder modules are not necessary. However, the correct order of the I/O-
modules has to be observed.
Both lines of the BusHead can be filled with a maximum of 15 I/O-modules each.
I/O-modules at the line 1 are
inserted into the slots 1-15.
I/O-modules at the line 2 are
inserted into the slots 16-30.
Virtual module necessary for
the operation of LioN-Link
motion module
0942 UEM 783.