Technical Manual
LioN-Link PROFINET
Subject to change without notice!
Version 1.2 / August 2014
Page 16 of 30
6.
Configuring and commissioning
The configuration and commissioning of the LioN-Link BusHead described on the following pages was accomplished with the
help of the
STEP7
-software of the
Siemens AG
. In case of using a control system from another controller supplier please attend
to the associated documentation.
6.1.
GSDML-file
For the configuration of the BusHead in the control system a GSD-file in XML-format is required. This GSDML-file can be
downloaded from our homepage under
http://www.beldensolutions.com/en/Service/Downloadcenter/Software_Lumberg/index.phtml
.
On request the GSDML-file is also mailed by the support team.
The name of the file is as follows:
GSDML-v2.2-Lumberg Automation-LioN Link-yyyymmdd.xml,
in which „yyyymmdd“ expresses the release date of the file.
In
STEP7
you create a new project and open the hardware manager
HW-Config
. By the menu item
Options – Install GSD File…
and the subsequent dialogue the GSDML file is installed. The LioN-Link system with the PROFINET BusHead is displayed
afterwards in the hardware catalogue.
6.2.
MAC addresses
The BusHead gets three MAC addresses assigned on delivery. These are unique and cannot be changed by the user.
6.3.
SNMP
The BusHead supports the Ethernet network protocol SNMP (Simple Network Management Protocol). The information of the
network management is presented according to the MIB-II (Management Information Base) which is defined in the RFC 1213.