Electrical installation
BEKOMAT® 33U / 33U CO
17
Pos: 53 / Beko Technische Dok um ent at ion/ Über schr if t en/ 1/ Elekt r ische I nst allat ion @ 0\ m od_118363850 7355_2 901. docx @ 5619 @ 1 @ 1
11 Electrical installation
Pos: 54 / Beko Technische Dok um ent at ion/ Sich er heit / G ef ahr Net zspannung 1 s/ w @ 0\ m od_1184148186948 _2901. docx @ 5796 @ @ 1
Danger!
Supply voltage!
There is the risk of an electric shock involving injury or death when coming into contact
with non-insulated components carrying supply voltage.
Pos: 55 / Beko Technische Dok um ent at ion/ Sich er heit / M aßnahm en Net zspann ung BM 31U/ 32U/ 33 U @ 7\ m od_13904671 97804_2 901. docx @ 38043 @ @ 1
Measures:
•
During electric installations, all regulations in force need to be adhered to (e.g. VDE 0100 / IEC 60364).
•
When the control unit is open, service and installation works must only be undertaken when the
system is deactivated.
•
The removed control unit has no IP degree of protection.
•
All types of electrical works must be carried out by authorised and qualified personnel only.
Pos: 56 / Beko Technische Dok um ent at ion/ I nst allat ion/ B EKO M AT/ E lekt r I nst allat ion H inwe ise BM 32 U/ 33U al lg. @ 4\ m od_135772888407 9_2901. docx @ 29514 @ @ 1
Note:
Power supply connection:
1.
Read the permissible supply voltage on the type
plate and make sure this voltage is observed.
2. For the supply voltage, a reliably accessible sepa-
rator must be provided close-by (e.g. power plug
or switch), which separates all current-carrying
conductors.
3. At a low-voltage supply
(< 50 VAC / < 75 VDC), only use a protective ex-
tra-low-voltage.
4. Carry out installation in accordance with
VDE 0100 / IEC 60364.
5. Observe the terminal assignment.
6. Do not install when the device is energised.
7. Unscrew the screws (1) and remove the upper
part of the cover (2).
8. Unscrew the threaded cable connection (3), re-
move the plug (if there is one), and lead the cable
(4) for the power supply through.
9. Connect the cable (4) with terminals X1 (1.1, 1.2)
(5).
10.Install the cables as shown (see also terminal as-
signment in the following text).
11.Tighten the threaded cable connection (3) with a
slightly sealing effect.
12.Put on the upper part of the cover (2) and tighten
the screws (1) fingertight.