3.4.3.3 Changing interface parameters
INFORMATION
BEKO TECHNOLOGIES configuration tools!
i
BEKO
TECHNOLOGIES recommends using the Software Integrator to change the interface
parameters. The software can be downloaded from the
BEKO
TECHNOLOGIES homepage
(see “1.1 Contact” on Page 5).
For connection to a PC,
BEKO
TECHNOLOGIES recommends using the
Integrator Hardware Kit (for ordering information see chapter “11.2 Accessories” on Page
59).
This process is used to change interface parameters required for communication.
1. Write the value 0xAC1D (decimal: 44061) to the Holding Register 0x1392 (decimal: 5010).
2. Write the parameter to the Holding Register 0x07D0 (decimal: 2000).
Description / explanation
HighByte:
See the following table
LowByte:
Modbus Client address 1 … 246
Example value:
0x070A (decimal: 1802)
For interface parameters see table Index 0x07 (decimal: 7)
Client address 0x0A (decimal: 10)
3. To save the settings write the value 0xBA5E (decimal: 47710) to the Holding Register 0x139C (decimal: 5020).
4.
Switch the product off and switch it back on again.
0
The changes will go into effect approx. 10 seconds after the restart.
Parameter - HighByte
Parameter - HighByte
Selection
Baud rate
[Bd]
Parity
Stop Bit
Selection
Baud rate
[Bd]
Parity
Stop Bit
0x00
4800
No
2
0x0C
57600
No
2
0x01
4800
Even
1
0x0D
57600
Even
1
0x02
4800
Odd
1
0x0E
57600
Odd
1
0x03
9600
No
2
0x0F
76800
No
2
0x04
9600
Even
1
0x10
76800
Even
1
0x05
9600
Odd
1
0x11
76800
Odd
1
0x06
19200
No
2
0x12
115200
No
2
0x07
19200
Even
1
0x13
115200
Even
1
0x08
19200
Odd
1
0x14
115200
Odd
1
0x09
38400
No
2
0x0A
38400
Even
1
0x0B
38400
Odd
1