Programming
TX1200
33
Version: 1.1
nControlMode : E_MP_EV_V4_ControlMode;
rBusFailPosition : LREAL;
nCommunicationWatchdog : UINT;
bSetpointSource : BOOL;
nSensor1Type : E_MP_VRU_Sensor1Type;
rVmin : LREAL;
rVmax : LREAL;
rVnom : LREAL;
rPnom : LREAL;
rPmax : LREAL;
nDeltaTLimitation : E_MP_EV_V4_DeltaTLimitation;
nDeltaTManagerStatus : E_MP_EV_V4_DeltaTManagerStatus;
rSetpointDeltaT : LREAL;
rSetpointAbsFlowDeltaT : LREAL;
arSerialNumber : ARRAY[0..1] OF DWORD;
bSelectMeterRegister : BOOL;
bBusy:
this bit is set for as long as the function block is active.
bError:
the output becomes TRUE as soon as an error occurs. This error is described via the
iErrorId
variable.
iErrorId:
this output outputs an error code in the event of an error (see
).
bError
goes
TRUE at the same time.
st_MalfunctionService:
malfunction and service information (see
St_MP_EV_V4_MalfunctionServiceInfo
).
nControlMode:
).
rBusFailPosition:
bus failure position in % (0...100). Not functional (reserved for future extensions).
nCommunicationWatchdog:
communication watchdog in sec (0...3600). Not functional (reserved for future
extensions).
bSetpointSource:
TRUE = bus; FALSE = analog.
nSensor1Type:
rVmin:
min setpoint in % (0...Vmax). Refers to Vnom and is taken into account when control mode = flow
control.
rVmax:
max setpoint in % (25...100). Refers to Vnom and is taken into account when control mode = flow
control.
rVnom:
nominal volume flow rate in l/s (0...100).
rPnom:
nominal output in kW (0...21.5).
rPmax:
max setpoint in % (5...100). Refers to Pnom and is taken into account if control mode = power
control.
nDeltaTLimitation:
specifies whether the device responds to a low delta T (see
nDeltaTManagerStatus:
indicates the status of the DeltaT Manager (see
E_MP_EV_V4_DeltaTManagerStatus
).
rSetpointDeltaT:
setpoint DeltaT in K (0...60). Is taken into account if DeltaT limitation is active (not
disabled).
rSetpointAbsFlowDeltaT:
setpoint Abs flow DeltaT in l/s (0...100.000). Considered when DeltaT limitation is
set to DeltaT Manager scaled.
arSerialNumber:
serial number of the device.
bSelectMeterRegister:
FALSE = certified meter; TRUE = lifetime meter.