Programming
TX1200
59
Version: 1.1
bSetpointSourcesRead : BOOL;
bOperationModeRead : BOOL;
nSensor1TypeRead : E_MP_VRU_Sensor1Type;
nApplication : E_MP_VRU_Application;
bControlMode : BOOL;
nRoomPressureCascade : E_MP_VRU_RoomPressureCascade;
bBusy:
this bit is set for as long as the function block is active.
bError:
the output becomes TRUE as soon as an error occurs. This error is described via the
iErrorId
variable.
iErrorId:
this output outputs an error code in the event of an error (see
).
bError
goes
TRUE at the same time.
rNominalVolumeticFlow:
nominal volume flow in m³/h (0...60.000).
rNominalDeltaPressure:
nominal differential pressure in Pa (0...10.000).
rMinRead:
min in % (0...
rMax
).
rMin
must be smaller than
rMax
.
rMaxRead:
max in % (20...100 %).
bSetpointSourcesRead:
TRUE = bus; FALSE = analog
bOperationModeRead:
TRUE = overpressure; FALSE = negative pressure
nSensor1TypeRead:
.
nApplication:
visualization of the
selected by the manufacturer.
bControlMode:
visualization of the control function selected by the manufacturer. TRUE = volume flow rate
control; FALSE = position control
nRoomPressureCascade:
room pressure
6.2.22
MP_VRU_Process
This function block is suitable for VAV actuators VRU-D3-BAC, VRU-M1-BAC and VRU-M1R-BAC (max. 8
slaves). For more information please visit