Programming
TX1200
32
Version: 1.1
This function block is used to configure the Energy Valve actuators EV..R2+... (V4). For more information
please visit
.
MP_Address
is used to specify the MP-Bus device with which the function block is to communicate.
bStart
activates communication with the MP-Bus device.
bBusy
indicates that the function block is active.
bError
is
used to indicate an error in communication with the actuator. The type of the error can be read with
iErrorId
.
VAR_INPUT
MP_Address : USINT := 1;
bStart : BOOL;
bRead_Write : BOOL;
strDataKL6771 : DataKL6771;
rVmax_Write : LREAL := 100;
rVmin_Write : LREAL;
bSetpointSource_Write : BOOL := TRUE;
nSensor1Type_Write : E_MP_VRU_Sensor1Type;
nControlMode_Write : E_MP_EV_V4_ControlMode := 1;
rBusFailPosition_Write : LREAL;
nCommunicationWatchdog_Write : UINT;
rPmax_Write : LREAL := 100;
nDeltaTLimitation_Write : E_MP_EV_V4_DeltaTLimitation;
rSetpointDeltaT_Write : LREAL := 1.0;
rSetpointAbsFlowDeltaT_Write : LREAL;
bSelectMeterRegister_Write : BOOL;
MP_Address:
MP-Bus address of the slave.
bStart:
a positive edge starts the function block.
bRead_Write:
if FALSE then READ only; if TRUE then READ and WRITE.
strDataKL6771:
the data structure with which the
function block must be linked (see
).
rVmax_Write:
max setpoint in % (25...100). Standard 100 %. Refers to Vnom and is taken into account
when control mode = flow control.
rVmin_Write:
min setpoint in % (0...Vmax). Vmin must be smaller than Vmax.
bSetpointSource_Write:
TRUE = bus; FALSE = analog.
nSensor1Type_Write:
sensor 1 type (see
nControlMode_Write:
control mode (see
).
rBusFailPosition_Write:
bus fail position in % (0...100). Not functional (reserved for future extensions).
nCommunicationWatchdog_Write:
communication watchdog in s (0...3600). Not functional (reserved for
future extensions).
rPmax_Write:
max setpoint in % (5...100). Standard 100 %. Refers to Pnom and is taken into account if
control mode = power control.
nDeltaTLimitation_Write:
determines whether the device responds to a low delta T (see
rSetpointDeltaT_Write:
setpoint delta T in K (0...60). Standard 1.0K. Is taken into account if the delta T
limitation is active (not disabled).
rSetpointAbsFlowDeltaT_Write:
setpoint Abs flow delta T in l/s (0...100.000). Considered when Delta T
limitation is set to "Delta T Manager scaled".
bSelectMeterRegister_Write:
FALSE = certified meter; TRUE = lifetime meter.
VAR_OUTPUT
bBusy : BOOL;
bError : BOOL;
iErrorId : MP_Error;
st_MalfunctionService : St_MP_EV_V4_MalfunctionServiceInfo;