Programming
TX1200
29
Version: 1.1
strDataKL6771:
the data structure with which the
function block must be linked (see
).
TMpolling:
the time for which the function block should address the actuator. Default 10 s, minimum time
1 s.
VAR_OUTPUT
bBusy : BOOL;
bError : BOOL;
iErrorId : MP_Error;
ActValue : WORD;
bMP_Sensor_Digi : BOOL;
iMP_Sensor_Analog : INT;
AirVolume_m3h : WORD;
iVnom_m3h : INT;
act_MaxVol : INT;
act_MinVol : INT;
bErr_ActHunt : BOOL;
bErr_MecTrv : BOOL;
bErr_MecOvld : BOOL;
rTemperature : LREAL;
bBusy:
this bit is set for as long as the function block is active.
bError:
the output becomes TRUE as soon as an error occurs. This error is described via the
iErrorId
variable.
iErrorId:
this output outputs an error code in the event of an error (see
).
bError
goes TRUE
at the same time.
ActValue:
contains the current position of the actuator (0...100 %).
bMP_Sensor_Digi:
if an analog sensor is connected, its value is indicated through this variable.
iSensorTyp
must be "1".
iMP_Sensor_Analog:
if an analog sensor is connected, its value is indicated through this variable.
iSensorTyp
must be in the range "2...6".
AirVolume_m3h:
output of the volume flow rate in m³/h.
iVnom_m3h:
nominal air volume flow in m³/h. This output is available from version 1.12.0. VAV is read and
must be > 0. If 0, then the calculation of
AirVolume_m3h
is not correct.
act_MaxVol:
maximum set volume flow rate in %.
act_MinVol:
minimum set volume flow rate in %.
bErr_ActHunt:
actuator error, "Regulating oscillation"; the actuator is swinging backwards and forwards.
bErr_MecTrv:
actuator error, "Positioning angle exceeded"; the actuator has passed more than 10° beyond
the adaptation position.
bErr_MecOvld:
actuator error, "Overload"; the set position could not be reached.
rTemperature:
temperature in the channel in °C.
Содержание TwinCAT 2 TX1200
Страница 1: ...Manual EN TX1200 TwinCAT 2 PLC Library TcMPBus 2022 06 02 Version 1 1...
Страница 2: ......
Страница 79: ......