Programming
TX1200
73
Version: 1.1
6.4.2.2
MP_BUS_MPX_ERROR
Error messages of the "MPX" sensors (function block
TYPE MP_BUS_MPX_ERROR :
STRUCT
MP_BUS_MPX_TempSensorErr : BOOL;
MP_BUS_MPX_HumiditySensorErr : BOOL;
MP_BUS_MPX_CO2SensorErr : BOOL;
MP_BUS_MPX_VocSensorErr : BOOL;
END_STRUCT
END_TYPE
MP_BUS_MPX_TempSensorErr:
The temperature sensor is faulty.
MP_BUS_MPX_HumiditySensorErr:
The humidity sensor is faulty.
MP_BUS_MPX_CO2SensorErr:
The CO2 sensor is faulty.
MP_BUS_MPX_VocSensorErr:
The VOC sensor is faulty.
6.4.2.3
MP_Serial_Number
Serial number of the device.
TYPE MP_Serial_Number :
STRUCT
YearAndWeek : WORD;
DayAndNumber : WORD;
DeviceFamily : BYTE;
TestStation : BYTE;
FamilySuffix : BYTE;
END_STRUCT
END_TYPE
YearAndWeek:
Year and week.
DayAndNumber:
Day and number.
DeviceFamily:
Device family.
TestStation:
Test station.
FamilySuffix:
Device family suffix.
6.4.2.4
St_MP_EV_V4_MalfunctionServiceInfo
Fault and service information.
TYPE St_MP_EV_V4_MalfunctionServiceInfo :
STRUCT
bNoCommunicationToActuator : BOOL;
bGearDisengaged : BOOL;
bActuatorCannotMove : BOOL;
bReverseFlow : BOOL;
bFlowSetpointNotReached : BOOL;
bFlowWithClosedValve : BOOL;
bActualFlowVnom : BOOL;
bFlowMeasurementError : BOOL;
bRemoteTempError : BOOL;
bIntegratedTempError : BOOL;
bCommToSensorInterrupted : BOOL;
bFreezeWarning : BOOL;
bGlycolDetected : BOOL;
bPowerSetpointNotReached : BOOL;
END_STRUCT
END_TYPE
bNoCommunicationToActuator:
no communication to the actuator.
bGearDisengaged:
gear disengaged.