Commissioning/Configuration
EP4174-0002
53
Version: 1.1.0
Index 1601 AO RxPDO-Map Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
1601:0
AO RxPDO-Map Ch.2 PDO Mapping RxPDO 2
UINT8
RO
0x01 (1
dec
)
1601:01
SubIndex 001
1. PDO Mapping entry (object 0x7010 (AO outputs Ch.2),
entry 0x11 (Analog output))
UINT32
RO
0x7010:11, 16
Index 1602 AO RxPDO-Map Ch.3
Index (hex) Name
Meaning
Data type
Flags
Default
1602:0
AO RxPDO-Map Ch.3 PDO Mapping RxPDO 3
UINT8
RO
0x01 (1
dec
)
1602:01
SubIndex 001
1. PDO Mapping entry (object 0x7020 (AO outputs Ch.3),
entry 0x11 (Analog output))
UINT32
RO
0x7020:11, 16
Index 1603 AO RxPDO-Map Ch.4
Index (hex) Name
Meaning
Data type
Flags
Default
1603:0
AO RxPDO-Map Ch.4 PDO Mapping RxPDO 4
UINT8
RO
0x01 (1
dec
)
1603:01
SubIndex 001
1. PDO Mapping entry (object 0x7030 (AO outputs Ch.4),
entry 0x11 (Analog output))
UINT32
RO
0x7030:11, 16
Index 1C00 Sync manager type
Index (hex) Name
Meaning
Data type
Flags
Default
1C00:0
Sync manager type
Using the sync managers
UINT8
RO
0x04 (4
dec
)
1C00:01
SubIndex 001
Sync-Manager Type Channel 1: Mailbox Write
UINT8
RO
0x01 (1
dec
)
1C00:02
SubIndex 002
Sync-Manager Type Channel 2: Mailbox Read
UINT8
RO
0x02 (2
dec
)
1C00:03
SubIndex 003
Sync-Manager Type Channel 3: Process Data Write
(Outputs)
UINT8
RO
0x03 (3
dec
)
1C00:04
SubIndex 004
Sync-Manager Type Channel 4: Process Data Read (In-
puts)
UINT8
RO
0x04 (4
dec
)
Index 1C12 RxPDO assign
Index (hex) Name
Meaning
Data type
Flags
Default
1C12:0
RxPDO assign
PDO Assign Outputs
UINT8
RW
0x04 (4
dec
)
1C12:01
Subindex 001
1. allocated RxPDO (contains the index of the associated
RxPDO mapping object)
UINT16
RW
0x1600
(5632
dec
)
1C12:02
Subindex 002
2. allocated RxPDO (contains the index of the associated
RxPDO mapping object)
UINT16
RW
0x1601
(5633
dec
)
1C12:03
Subindex 003
3. allocated RxPDO (contains the index of the associated
RxPDO mapping object)
UINT16
RW
0x1602
(5634
dec
)
1C12:04
Subindex 004
4. allocated RxPDO (contains the index of the associated
RxPDO mapping object)
UINT16
RW
0x1603
(5635
dec
)
Index 1C13 TxPDO assign
Index (hex) Name
Meaning
Data type
Flags
Default
1C13:0
TxPDO assign
PDO Assign Inputs
UINT8
RW
0x00 (0
dec
)