Product overview
BK3xx0
10
Version: 4.3.0
Technical data
Type
BK3000, BK3010
BK3100, BK3110
BK3120
LC3100
Number of Bus Terminals 64
64 (255 with K-bus exten-
sion)
64
Digital peripheral signals
512 inputs/outputs (BK3x00)
256 inputs/outputs (BK3x10)
max. 1020 inputs/outputs 256 inputs/outputs
Analog peripheral signals 128 inputs/outputs (BK3x00)
max. 64 inputs/outputs
-
Configuration possibility
Via the KS2000 configuration software or the controller
Max. number of bytes
(inputs and outputs)
BK3000: 244 bytes
BK3100:
64 bytes (DP and FMS oper-
ation)
128 bytes (DP operation
only)
128 bytes
32 bytes
BK3010: 32 bytes
BK3110: 32 bytes
Baud rate (automatic de-
tection)
up to max. 1.5
Mbaud
up to max. 12 Mbaud
Bus connection
1 x D-sub plug, 9-pin with shielding
spring-loaded terminals
Power supply
24 V
DC
(-15 % /+20 %)
Input current
70 mA + (total K-bus current)/4, 500 mA max.
(BK3x00)
70 mA + (total K-bus current)/4, 200 mA max.
(BK3x10)
70 mA + (total K bus cur-
rent)/4, max. 500 mA
70 mA + (total K bus cur-
rent)/4, max. 200 mA
Starting current
2.5 x continuous current
Recommended fuse
maximum 10 A
K-bus current up to
1750 mA (BK3x00)
500 mA (BK3x10)
1750 mA
500 mA
Power contact voltage
maximum 24 V
DC
Power contact current
load
maximum 10 A
Electrical isolation
Power contact / supply / fieldbus
Power supply / fieldbus
Dielectric strength
500 V (power contact / supply / fieldbus)
500 V (supply / fieldbus)
Weight
approx. 170 g
approx. 150 g
approx. 170 g
approx. 100 g
Permissible ambient tem-
perature (operation)
0°C … +55°C
-25°C … +60°C
0°C … +55°C
Permissible ambient tem-
perature (storage)
-25°C … +85°C
Permissible relative hu-
midity
95% (no condensation)
Vibration/shock resis-
tance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approvals
, cULus,
GL, IECEx