Product overview
BK3xx0
12
Version: 4.3.0
Technical data BK3150
Type
BK3150
Number of Bus Terminals
64 (255 with K-bus extension)
Digital peripheral signals
256 inputs/outputs (BK3x10)
Analog peripheral signals
128 inputs/outputs (BK3x00)
Configuration possibility
Via the KS2000 configuration software or the
controller
Max. number of bytes
(inputs and outputs)
128 bytes (DP operation only)
Baud rate (automatic detection)
up to max. 12 Mbaud
Bus connection
1 x D-sub plug, 9-pin with shielding
Power supply (Us)
24 V
DC
(-15% /+20%) Use a 4 A fuse or an
NEC
Class 2
power supply to meet the UL requirements!
Input current (Us)
70 mA + (total K bus current)/4, max. 320 mA
Starting current (Us)
2.5 x continuous current
K-bus current (5 V)
up to hardware version 04: 1000 mA
from hardware version 05: 1750 mA
Power contact voltage (Up)
maximum 24 V
DC
Power contacts current load (Up)
maximum 10 A
Recommended backup fuse (Up)
maximum 10 A
Electrical isolation
Power contact / supply / fieldbus
Dielectric strength
500 V (power contact / supply / fieldbus)
Weight
approx. 100 g
Permissible ambient temperature (operation)
-25°C … +60°C
Permissible ambient temperature (storage)
-25°C … +85°C
Permissible relative humidity
95% (no condensation)
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approvals
CE,
, cULus