Parameterization and commissioning
BK3xx0
37
Version: 4.3.0
Byte
Bit
Value Description
GSD file
10
0-1
00
bin
Reaction to PROFIBUS error: K-bus cycle is abandoned (default,
digital outputs become 0, complex outputs are set to a configured
substitute value) (see
)
Standard
01
bin
Reaction to PROFIBUS error: K-bus outputs become 0
10
bin
Reaction to PROFIBUS error: K-bus outputs remain unchanged
10
2-3
00
bin
Reaction to K-bus error: DP data exchange is abandoned (default)
(see
Standard
01
bin
Reaction to K-bus error: DP inputs set to 0
10
bin
Reaction to K-bus error: DP inputs remain unchanged
11
3-6
X
Maximum length of the diagnostic data. Allowed values: 16, 24, 32, 40,
48, 56, 64 (see
)
Extended
12
0-1
0
bin
If K-bus mode is synchronous: Standard synchronous mode (default)
(see
Extended
01
bin
If K-bus mode is synchronous: synchronous mode with optimized input
update (one cycle)
10
bin
If K-bus mode is synchronous: synchronous mode with optimized input
update (two cycles)
12
4-7
0
bin
Maximum DP buffer lengths not changed
Extended
12
4-7
15
The maximum DP buffer lengths are changed using the values from
UserPrmData 37-40 (see
Extended
13
0-7
X
Delay time (in µs) high byte (see
Extended
14
0-7
X
Delay time (in µs) low byte (see
)
Extended
15-30 0-7
X
Assignment of Bus Terminals 1 to 64 (see
)
Extended
31-36 0-7
-
Reserved
Extended
37
0-7
X
Maximum length of the input data (see
)
Extended
38
0-7
X
Maximum length of the output data (see
)
Extended
39
0-7
X
Maximum length of the diagnostic data (see
)
Extended
40
0-7
X
Maximum length of the configuration data (see
Extended
41-56 0-7
X
Assignment of terminals 65 to 128 (see
)
Extended