Mounting and wiring
BK3xx0
29
Version: 4.3.0
3.4.5
PROFIBUS cabling
3.4.5.1
PROFIBUS Connection
M12 round connector
The M12 socket is inverse-coded and has five pins. Pin 1 transfers 5 V
DC,
pin 3 transfers GND for the active
termination resistor. These must never be misused for other functions, as this can lead to destruction of the
device.
Pins 2 and 4 transfer the PROFIBUS signals. These must never be swapped over, as this will prevent
communication. Pin 5 transfers the shield, which is capacitively connected to the base of the Fieldbus Box.
Pin assignment M12 socket (-B310)
Fig. 18: Pin assignment M12 socket (-B310)
Pin assignment M12 socket/plug connector (-B318)
Fig. 19: Pin assignment M12 socket/plug connector (-B318)
Nine-pin D-Sub
Pin 6 transfers 5 V
DC,
pin 5 transfers GND for the active termination resistor. These must never be misused
for other functions, as this can lead to destruction of the device.
Pins 3 and 8 transfer the PROFIBUS signals. These must never be swapped over, as this will prevent
communication.
Pin assignment of the PROFIBUS D-sub socket
Fig. 20: Pin assignment of the PROFIBUS D-sub socket
PROFIBUS wire colors
PROFIBUS line
M12
D-Sub
B red
Pin 4
Pin 3
A green
Pin 2
Pin 8