40
Part No. 6-847703-00 Rev. C00
22. Open vent valve to create a small flow of gas
through manifold. Verify output pressure
gauge reading of reserve header regulator is
as indicated in Table 1 (Reserve Header
Regulator). If pressure value is not correct,
refer to Reserve Header Regulator Adjustment
procedure.
23. Close vent valve. Watch reserve header
regulator output pressure gauge for at least
five minutes. Reading may be slightly higher
without vent flow. Verify readings do not
continue to increase.
24. Close all high-pressure cylinders connected to
reserve header. Open vent valve slightly so
that cylinder contents pressure gauge on
reserve header regulator drops slowly. Verify
power supply red “RESERVE LOW” light
illuminates when pressure drops to value in
Table 1 (Reserve Low Switch). If pressure is
not correct, refer to Reserve Low Switch
Adjustment procedure.
25. Close vent valve. If manifold is connected to a
master alarm panel, verify “SECONDARY
SUPPLY”, “RESERVE IN USE” and
“RESERVE LOW” alarms are activated.
26. Slowly open one cylinder on high-pressure
reserve header. Verify the following:
• Power supply red “RESERVE LOW” light
turns off.
• If connected to a master alarm panel,
“RESERVE LOW” alarm cancels.
• If connected to a master alarm panel,
“SECONDARY SUPPLY” and “RESERVE
IN USE” alarms remain activated.
27. Slowly open one high-pressure cylinder on
right side of manifold. Verify the following:
• Power supply red “RESERVE IN USE”
light turns off.
• Right bank red “EMPTY” light turns off.
• Right bank green "IN USE" light
illuminates.
• If connected to a master alarm panel,
“RESERVE IN USE” alarm cancels.
• If connected to a master alarm panel,
“SECONDARY SUPPLY” alarm remains
activated.
28. Slowly open one liquid container on left side.
Verify the following:
• Left bank red “EMPTY” light turns off.
• Left bank green “IN USE” light illuminates.
• Right bank green “IN USE” light turns off.
• Right bank yellow “READY” light
illuminates.
• If connected to a master alarm panel,
“SECONDARY SUPPLY” alarm cancels.
29. Open two right side line regulator isolation
valves.
30. Close all left bank liquid containers and right
bank high-pressure cylinders. Close all
cylinders on high-pressure reserve header.
31. Record pressure readings of manifold’s left
and right bank pressure gauges. Record
pressure reading of reserve header cylinder
contents gauge.
32. Verify that after 15 minutes, all three pressure
gauge readings have not changed.
33. Slowly open all liquid containers and high-
pressure cylinders on both banks of manifold.
Slowly open all cylinders on high-pressure
reserve header.
34. Reinstall manifold control panel cover.
35. Open 3/4" source shut-off valve.
Testing and Adjustments