background image

10

Medical Gas Central Alarm - Medipoint 125 Digital Alarm

4233500107.03

1.6.2  Power supply printed circuit board

The power supply PCB is retained inside the alarm panel 

back box with four retaining studs and connects to the 

processor  PCB  multi-way  ribbon  cable  by  polarised 

connectors.  The  power  supply  PCB  incorporates  four 

mains  terminals  (2  Earth,  Neutral  and  Live,  see  figure 

8)  connected  to  a  matching  plug/socket  combination 

to  accept  the  mains  electrical  power  supply,  which 

preferably  should  be  from  an  essential  circuit,  and 

enables connection of flying earth leads which electrically 

bond the assembly.  

A filter protects the alarm system from possible spikes 

or disturbances of the incoming electrical power supply 

and an integral transformer provides 24 V d.c. Supplies 

to  operate  the  alarm  circuits  and  power  the  pressure 

sensors.  A  5x20mm  fuses  to  BS  EN  60127  protect  the 

power  supply  circuits.  F1  is  rated  at  500mA  for  230V 

supplies and (see figure 8). 

In  order  to  prevent  inadvertent  cross  connection,  the 

mains  electrical  power  supply  plug  and  socket  is  not 

mechanically  compatible  with  any  other  connection  to 

the PCB. 

A  miniature  ’Maintenance  Mute’  push  button  (see 

figure  8)  is  fitted  on  the  power  supply  PCB  and  is 

accessible with the alarm panel front cover open. With 

an alarm condition displayed, operation of this button 

’permanently’  disables  audible  reinstatement  for  that 

particular  displayed  alarm  condition  only.  This  facility 

is designed for use when the plant or pipeline is shut-

off  for  a  prolonged  period.  On  returning  the  pipeline 

pressure to NORMAL this feature automatically re-sets 

without further manual selection.

Each  channel  (designated  1  to  5)  incorporates  five 

terminals  (figure  8)  which  are  for  connecting  to  the  

medical gas source equipment.

A relay (complete with optional line contact monitoring 

circuit) suitable for switching 50V and a maximum of 0.5 

Amps  is  fitted  to  the  power  supply  PCB  (see  figure  8). 

The relay has volt free, normally open contacts and two 

terminals (N/O and C) enable connection by a matching 

plug/socket  combination  to  either  a  Medipoint  central 

alarm system or other suitable system. The line contact 

monitoring  circuit  can  be  from  the  on  screen  setup 

menus.  The  relay  is  de-energised  and  contacts  open 

when  any  of  the  twelve  alarm  conditions  are  initiated. 

Terminals are also provided to enable connection of a 

remote  audible  warning  device  (AUD+  and  AUD-)  (see 

figure 8).

It is recommended that the input cables from the source 

equipment and data transmission are installed separate 

from the mains cable.

Figure 8 - Power supply PCB.

Mains 

Fuse [F1]

Mains

Filter

24V DC

Power supply

Remote Audible

Connection [+] [-]

Output Relay For Transmitting Single Event Alarm

[COMMON] [N/O]

Gas Service Connections, Channel 1-5

Data Transmission connections

IN [A] [B], out [A] [B] and [Screen]

Main Power Connection

[BONDING EARTH]

[MAINS EARTH] 

[NEUTRAL] [LIVE]

Maintenance

Mute

Multi way ribbon cable 

connector to processor PCB

Backup

Battery Pack

End of Line 

Resistors 

Switches

Содержание 8102371401

Страница 1: ...Operation and Maintenance Instructions Medical Gas Central Alarm Medipoint 125 Digital Alarm Part number 4233500107 Revision 03 Jan 2021...

Страница 2: ...hone 44 0 1246 474242 Email gbn info beaconmedaes com Website Contacts www beaconmedaes com BeaconMed s reserves the right to make changes and improvements to update products sold previously without n...

Страница 3: ...in screen 3 6 Exit Setup Screen 3 7 Confi guration Menu Map 4 0 Commissioning 4 1 Alarm panel test 4 2 Checking the slave relay output 4 3 Checking the remote audible warning 4 4 Medical gas alarm fau...

Страница 4: ...ckaged and stored in controlled conditions Environmental Operating Conditions Adverse environmental conditions and harsh abrasives or chemicals may cause damage to the unit Environmental Protection Di...

Страница 5: ...rammed from on screen menus to provide a fully flexible alarm system Allowing the panels to be adapted to suit any hospital s medical gas monitoring requirements see section 1 12 for programming detai...

Страница 6: ...nt of any defect within the monitored functions the SYSTEM ALARM LED illuminates flashing accompanied by the audible warning and the defective gas service alarm display status bar illuminates An inter...

Страница 7: ...operty and shall not without our permission be altered ATLAS COPCO STANDARD Class Tolerances if not indicated according to Material Treatment Name Scale Family Drawing owner Secrecy Class 1102 K Compa...

Страница 8: ...p to four fault conditions yellow or red flashing alarm conditions to show the gas service status All alarm conditions are illuminated by a flashing display and accompanied by an audible warning Each...

Страница 9: ...on these PCB s which are interconnected by means of a multi way ribbon cable and polarised connector see figure 2 3 The area central alarm internal electrical installation complies with all relevant...

Страница 10: ...cular displayed alarm condition only This facility is designed for use when the plant or pipeline is shut off for a prolonged period On returning the pipeline pressure to NORMAL this feature automatic...

Страница 11: ...nnections have 5 terminals each See table 2 for details for standard options Each gas service and fault legend is also fully customisable through the on screen setup menus TABLE 2 GAS SERVICE CONNECTI...

Страница 12: ...uired by the contract specification Feed cables into the box leaving 400mm to 75 150 105 105 7 260 5 TOP 40 40 40 40 17 20 KNOCKOUT SEGMENTS 200 17 45 2 0 KNOCKOUT SEGMENTS BACKBOX SURFACE Figure 10 B...

Страница 13: ...Power supply PCB installation No Description QTY 1 Back Box 1st fix supply N A 2 Power supply PCB 2nd fix supplied loose 1 3 PCB Spacer 2nd fix supplied loose 4 4 M3 Nut 2nd fix supplied loose 4 5 M3...

Страница 14: ...nections No Description QTY 1 Earth cable 2nd fix supplied assembled 1 2 M3xNut 2nd fix supplied loose 4 3 M3 washer 2nd fix supplied loose 4 Typical earth stud assembly 2 2 3 1 Alarm Door Earth Stud...

Страница 15: ...igure 15 Alarm data connection MP125D 1 S1 ON IN OUT A B A B S MP125D 2 S1 OFF IN OUT A B A B S MP125D 3 S1 ON IN OUT A B A B S Note S terminal is for connecting the screen cable 2 2 6 Remote audible...

Страница 16: ...mmissionedimmediately disconnect the standby battery Connect electrical power supply wires to electrical power supply plug terminals E N and L 1 2 Figure 21 Alarm door security fastener No Description...

Страница 17: ...aracters Icons Icon Description Enter Key TAB key Moves to next field and highlights text Highlighted text will be overwritten on next key press Tick key Apply update and takes you to the main screen...

Страница 18: ...e Alarm setup 2 screen or press the Exit Icon to go back to the main operating screen 3 4 Alarm Setup Screen 1 Figure 26 The following steps describes the setup process for the alarm setup screen 1 3...

Страница 19: ...e new numerical password Press the TAB key or press the next field to go to the next field Confirm Use the num pad to enter the password again Press the ENTER key or press anywhere on the screen away...

Страница 20: ...setup process for the main gas service setup screen Figure 27 Main Gas Service Setup screen Special Characters Icons Icon Description Previous Icon Takes you to the previous menus screen Next Icon Tak...

Страница 21: ...k to set as inputs tick to set as remote transmission Press to toggle between the options 3 5 6 Location Special Characters Icons Description Exit Icon Takes you back to the main screen O2 Oxygen Gas...

Страница 22: ...elds will be editable 3 5 7 1 Standard gas options These fields allow for selecting the source equipment type available for the standard gas type selected Press on the matching equipment type to auto...

Страница 23: ...etup screen Figure 33 Main Gas Service Setup screen Special Characters Icons Icon Description Previous Icon Takes you to the previous menus screen Next Icon Takes you to the next menus screen Exit Ico...

Страница 24: ...key press Previous Icon Takes you to the previous menus screen Next Icon Takes you to the next menus screen Exit Icon Takes you back to the main screen Reject Icon Rejects changes Accept Icon Accepts...

Страница 25: ...6 shows examples of all status flashing See table 6 in section 5 Operation of the Medipoint 125 Digital alarm for troubleshooting Figure 36 Alarm Test Button example 6 gas 4 2 Checking the slave relay...

Страница 26: ...e table 2 section 1 8 for full list of standard gas service fault legends Check that the MUTE switch operates satisfactorily Press the audible alarm will be silenced and the mute icon will show on scr...

Страница 27: ...ED is flashing red The audible alarm is active See figure 39 fro example Figure 39 Example Gas service 1 connection fault 4 5 3 Input Reconnect Reconnect the input plug to gas channel System will retu...

Страница 28: ...d and the alarm condition remains the audible warning will re sound after 15 mins and a further MUTE selection will be required Should a further alarm condition occur after the panel has indicated a f...

Страница 29: ...mple shows gas service fault 4 Power LED Green On System Fault Black Off Gas Status Bar Red Flashing Audible Active Audible Mute Gas service fault flashing Mute activated Audible Silenced for 15 minut...

Страница 30: ...lank normal Yellow flashing fault Fault status 3 Blank Fault status 4 Blank normal Red flashing fault Manifold Control Systems Normal status Green normal blank during fault Fault status 1 Blank normal...

Страница 31: ...to the main screen automatically if a new alarm condition becomes active or after one minute if the alarm is not manually exited from the information screen 5 2 2 Data Logging Screen The data logging...

Страница 32: ...s distributors will be able to supply similar contracts in other areas CAUTION It is essential that only genuine BeaconMed ssparepartsarefittedduringmaintenance WARNING Obtain a work permit or equival...

Страница 33: ...33 Medical Gas Central Alarm Medipoint 125 Digital Alarm 4233500107 03 Figure 45a Alarm panel assembly details...

Страница 34: ...34 Medical Gas Central Alarm Medipoint 125 Digital Alarm 4233500107 03 Figure 45b Alarm panel assembly details...

Страница 35: ...e 5 year maintenance replace the LCD screen and backup butteries See maintenance procedures in 6 1 and figures 45a 45b for details 8 RECOMMENDED SPARES Table 8 details the list of recommended spares t...

Страница 36: ...2460 Atlas Copco Medical Ltd Telford Crescent Staveley Derbyshire S43 3PF UK Tel 44 0 1246 474242 www beaconmedaes com Atlas Copco Airpower n v Boomsesteenweg 957 2610 Wilrijk Belgium...

Отзывы: