Page
35
Temperature
Alarm
Threshold
Under
Voltage
Alarm
Threshold
Over
Voltage
Alarm
Threshold
Low
Current
Alarm
Threshold
Environmental
Sensors
Individual
Sensors
Environmental Sensor Configuration Menu
Sel M/P Identifier
1 2/1 MSP10
2 All Sensors
Enter Request :1
Sel Type Name Hi/En Lo/En St/En
1 Contact External Sensor1 N/A N/A Ds
2 Temperature External Sensor2 0/Ds 0/Ds N/A
Enter Request :2
Select 1),
to change the alarm for Internal Temperature: Enter the
Selection (Sel) Number and press Enter. Type a value in tenths of
a degree,
i.e.500 = 50.0
⁰
C
Sel M/P Identifier Tmp Lvl
1 2/1 MSP10 500
Select 2),
to change the alarm for Low Voltage: Enter the
Selection (Sel) Number and press Enter. Type a value in tenths of
a volt,
i.e 900 = 90.0 volts.
Sel M/P Identifier Lo V Lvl
1 2/1 MSP10 900
Select 3),
to change the alarm for over voltage: Enter the
Selection (Sel) Number and press Enter. Type a value in tenths of
a volt,
i.e 1300 =130.0 volts.
Sel M/P Identifier Hi V Lvl
1 2/1 MSP10 1300
Select 4),
to change the alarm for low current: Enter the Selection
(Sel) Number and press Enter. Type a value in tenths of a volt,
i.e
100 =10.0 amps
Sel M/P Identifier Low Curr
1 2/1 MSP10 0
Enter threshold value in tenths of
unit measurement (degrees,%,etc.):
Enter voltage threshold value in
tenths of a volt:
Enter low current threshold value in
tenths of an amp:
NOTE:
M/P = Module number and Port number; Identifier = this unit’s model number; Tmp Lvl =
temperature level, Lo V Lvl = low voltage level, Hi V Lvl = High voltage level, low Curr = Low
Current.
Select 1),
to change the limits of individual probes
Select 5),
to change the alarm limits for the Environmental probes:
If the unit does not have a sensor probe connected, the unit will display the following.
None of the installed devices support this option (no temperature probes installed).
Strike ENTER to continue
Enter voltage threshold value in
tenths of a volt:
Select either 1 or 2 (Sel) probe. (Hi/En) = Hi limit
Enabled, (Lo/En) = Low limit Enabled, (St/En) =
Sensor Trap enable