Page
34
Web
Server
Configuration
Menu 10: Web Server Configuration
Module
Name
RPC
Management
Menu 11: Network RPC Management
Select 1,
Web
Enable,
to enable or disable the web page feature,
Default is Enabled:
Web is ENABLED. Enable? (Y/N):
Web Login is DISABLED. Enable? (Y/N):
Web secure SSL connection is DISABLED. Enable? (Y/N):
Select 2,
Web
Login
Enable,
to enable or disable the login
window to the web page,
Default is Enabled
Select 3,
Web
Secure
Login
Enable,
to
enable or disable a secure web connection to
the web page,
Default is Disabled:
Select 4,
Web
Login
Inactivity
Timeout,
to set the
Inactivity timeout to the web page,
Default is zero
minutes:
Web Connection Inactivity Timeout is 0 minutes
Enter timeout, in minutes (<=120, 0 to disable) :
Web Enable........................1
Web Login Enable..................2
Web Secure Login Enable...........3
Web Login Activity Timeout........4
Exit..............................X
NOTE:
For this feature to operate the network port must have an IP Address assigned.
Type the unit’s IP Address on a web browser to get the unit web page, i.e.
http://70.150.140.95
NOTE:
The web page is a quick test to see if SNMP protocol is working in the unit, if SNMP has
been enabled.
IMPORTANCE:
Currently, all users who access the unit through the web page have administrator
privilege, unless a TACACS server and privilege levels are used for authentication.
Select 13 from the Network Port Configuration
Menu
for the Web Server Configuration menu:
IMPORTANCE:
If a user is still connected to the outlet controller menu, or the user does not
properly release the controller, the Web page will not update.
Module Name is: RPC
Enter Module Name (32 chars max):
Select 9, from the Network Configuration menu
to change the
unit name.
Host-controlled RPC Feature Configuration
Temperature Alarm Threshold........1
Under Voltage Alarm Threshold......2
Over Voltage Alarm Threshold.......3
Low Current Alarm Threshold........4
Environmental Sensors..............5
Outlet Groups......................6
Temperature units (degrees C/F)....7
Power Factor Threshold.............8
Select 10, from the Network Configuration
Menu
, to establish SNMP outlet traps used by a
remote SNMP Manager by creating outlet
groups and alarm thresholds.