2.7 AVAILABLE PUMP HEAD FOR CENTRAL HEATING
Only the third speed of the pump has to be used.
2.7 HAUTEUR D’ELEVATION DISPONIBLE POUR LE CHAUF-
FAGE CENTRAL
Seulement la troisième vitesse de la pompe doit être utilisée
2.8 SYSTEM VOLUME
Based on 30 p.s.i. / 2.11 bar safety valve setting
Vessel charge and initial system pressure bar 0.5 1.0 1.5
psi 7.25 14.5 21.7
Total water content of system using 2.2 gal / 10 l Litre 120 91 64
capacity expansion vessel (Can) gal 26.4 20 14
supplied with appliance (USA) gal 31.7 24 16.9
For systems having a larger capacity MULTIPLY
the TOTAL system capacity in litres (gallons) by 0.0833 0.109 0.156
the factor to obtain the TOTAL MINIMUM
expansion vessel capacity required in litres (gallons)
Note:
When the boiler is operating at maximum operating temperature,
providing heating with all radiators operating, the pressure gauge should
not indicate more than 25.5 p.s.i. / 1.8 bar. If the reading exceeds this
fi gure an additional expansion vessel is required.
2.8 VOLUME DU CIRCUIT
Basé sur le tarage de la soupape de sécurité à 30 p.s.i. / 2,11 bar
Pression initiale du circuit
bar 0.5 1.0 1.5
et de remplissage du vase
psi 7.25 14.5 21.7
Contenance totale en eau du circuit équippé d’un vase
Litre 120 91 64
d’expansion de
2,2 gal /
10 l de capacité,
(Can) gal 26.4 20 14
livré avec l’appareil
(USA) gal 31.7 24 16.9
Pour les circuits de capacité supérieure, MULTIPLIEZ
la contenance totale du circuit en litres par le facteur
0.0833 0.109 0.156
pour obtenir la contenance TOTALE MINIMALE
nécessaire du vase d’expansion.
Remarquez: Quand la chaudière est en service à la température maximale
et fournit du chauffage à tous les radiateurs, l’indicateur de pression
ne doit pas affi cher plus de 25,5 p.s.i. / 1,8 bar. Si la valeur affi chée est
supérieure, il est nécessaire d’ajouter un autre vase d’expansion.
2.9 BOILER SCHEMATIC
Central Heating Mode (Fig. 1)
1. With a demand for heating, the pump circulates water through the pri-
mary circuit.
2. The main burner ignites at low rate, then the air/gas system controls the
gas rate to maintain the heating temperature measured by the temperature
sensor.
3. When the fl ow temperature exceeds the setting temperature, a 3 minute
delay occurs before the burner relights automatically (anti-cycling). The
pump continues to run during this period.
4. When the demand is satisfi ed the burner is extinguished and the pump
continues to run for a period of 3 minutes (Pump Overrun).
2.9 SCHÉMA DE FONCTIONNEMENT DE LA CHAUDIÈRE
Mode chauffage central (Fig.1)
1. À la demande de chauffage, le circulateur refoule l’eau dans le circuit
principal.
2. Le brûleur principal s’allume à faible débit puis le système air/gaz
régle le débit du gaz pour maintenir la température de chauffage mesurée
par la sonde.
3. Lorsque la température dépasse la valeur d’étalonnage, le brûleur se
rallume automatiquement après un retard de 3 minutes (anti-cycling). Le
circulateur continue à tourner pendant cette période.
4. Lorsque la demande de chauffage a été satisfaite, le brûleur s’éteint
et le circulateur continue à tourner pendant 3 minutes (marche post-fonc-
tionnement).
Graph 1
Graphique 1
Water fl ow rate
/
Débit eau
(gal/h)
Available pump head (ftwc)
Hauter manimètrique (ftwc)