Discharging and earthing the test object
PD-TaD 80
56 / 74
822-188-3
On completion of cable testing or measurement the test object still carries a dangerous
voltage.
DANGER
Dangerous voltage in test object.
Danger of electric shock or risk of injury
Before touching, discharge, earth and short-circuit:
The test
object at the connection point and at the far end.
You may touch the plant parts that were under voltage only if they
are visibly earthed and short-circuited.
Connect the discharge and earth rod correctly to the station earth.
Only use the discharge and earth rod if its surface is clean and dry.
Hold the discharge and earth rod only at the handles!
Observe the minimum discharge period in accordance with the
capacitance of the test object.
12
D
ISCHARGING AND EARTH ING THE TEST OBJECT