Connecting the system
PD-TaD 80
36 / 74
822-188-3
Important:
To keep the connection cable between the PD-TaD and the test object short, place the
PD-TaD as close as possible to the test object.
To avoid interference due to partial discharge at the connection point, make sure the PD-
TaD is placed a sufficient distance away from metal and live parts.
If the connection point is higher up, put the PD-TaD on a substructure. Further
information: Chapter
Securing the PD-TaD 80 to the cross beam
(on page 33)
Keep all connections as short as possible.
Lay out the connection cables in such a way that no loops are created.
The numbering in the table gives the sequence of steps for connecting the test object.
No.
Cable
Step
1
Protective and auxiliary
earthing cables of the
cable test van (on cable
drum rack)
Earth the cable test van.
Further information: Additional manual for systems with diagnostics functions
2
Protective earthing
cable of PD-TaD 80
(flat copper strip)
Connect the PD-TaD 80 to the station earth (close to the test object cable
screen).
Further information: Chapter
Earth system
(on page 34)
In the cable test van on the connection box of the cable drum rack:
–
–
If present, connect the external emergency off unit to the connection box of
the cable drum rack (
port).
If you are not using an external emergency off unit, ensure that a jumper
plug is inserted into the
port on the connection box of the cable drum
rack.
3
PoE cable on hand
cable drum
Connect the PoE cable:
to the connection box (
PoE
port) and
to PD-TaD (
Power Box
port).
This is used for power supply and data transmission at the same time.
At the PD-TaD 80:
4
–
Connect the HF filter to the
HV IN
port.
Further information: Chapter
Connecting the HF filter to the PD-TaD 80
(on
5
HV connection cable of
the cable test van (on
cable drum rack)
Connect the screen of the HV connection cable to the
Screen (HV Cable)
port.
6
See above
Connect the HV connection cable to the HF filter on the
HV IN
port.
In the cable test van:
7
–
For titron® systems only:
If the connecting plug is inserted in the HV connection socket of the DU 80
discharge unit, unplug it and hang it in the holder.