en_BA_O200_IO-Link_V1.docx
18/34
Baumer Electric AG
15.08.2018/
Frauenfeld, Switzerland
4.3.4
Counter / SSC4
For each individual SSC a switching counter is implemented, which can be used as diagnosis data or also as
measurement value. The number of counts of each channel can also be mapped to the measurement data
channel MDC by adjusting the MDC source (See section 4.2.3).
Trigger of counter is on positive slope of related SSC.
By configuring SSC4, it is also possible to set up a binary signal related to the number of switchcounts of
SSC1. An auto-reset and timefilters are included, to be able to create a full-featured counter being able to
count lot sizes without any need to code software on the PLC.
As all SSCs, SSC4 can also be mapped to the digital output giving the possibility to create a stand-alone lot-
size counter.
In section 3.1, the signal path is decribed more detailed, to illustrate how the counter module is implemented.
In section 4.3.4.2 the behavior depending on the configuration is explained.
4.3.4.1
SSC4 Configuration
In general the SSC4 offers the same features as the SSC1 and SSC2 based on distance (See 4.3.2),
including also timefilters.
Exceptions:
-
No hysteresis settings as there are only incremental counts.
-
Additional parameters to adjust like
SSC4 Source
and
SSC4 Auto-Reset.
Parameter name
Short Description
Rights
Unit / Allowed values
SSC4 Setpoints.SP1
Set the number of counts at which the
SSC is set to active (or inactive if
inverted)
rw
Counts / 0 to 32759
SSC4 Setpoints.SP2
Set the number of counts at at which the
SSC is set to inactive (or active if
inverted)
-
only active if SSC is set to
window mode
rw
Counts / 0 to 32759
Parameter name
Short Description
Rights
Unit / Allowed values
SSC4 Config.Logic
Changes the Logic from NO to NC rw
-
Normal
-
Inverted
SSC4 Config.Mode
Selection of the switching mode
rw
-
Single Point
-
Window
SSC4 Config.Source
Selection of source for counter
function
rw
-
SSC1 Switch Counter
SSC4 Config.Auto Reset
Autoreset of switch counter if given
switch counts are reached.
If autoreset is switched from
disabled to enabled, the selected
switch counter-source is
automatically being reset to zero.
rw
-
Enabled
-
Disabled