en_BA_O200_IO-Link_V1.docx
20/34
Baumer Electric AG
15.08.2018/
Frauenfeld, Switzerland
4.4
Signal Processing
4.4.1
Measurement Mode (Only O200.G, S)
With this parameter pre-defined modes can be selected to achieve optimal results without much trial and
error.
Parameter name
Short Description
Rights
Unit / Allowed values
Measurement Mode
Choose measurement mode for
different applications
rw
-
High Speed
-
Standard
-
High Power
High Speed:
Ideal for fast moving objects. Sensors is adjusted for fastest response time. Detection ability identical to
Standard-Mode but with reduced ambient light immunity
Standard:
Standard setting with outstanding performance with the highest ambient light immunity.
High Power:
Twice the excess gain compared to Standard mode but with slower response time.
Reduced hysteresis due to better signal/noise ratio.
4.5
Input/Output Settings
4.5.1
Switching Output
Parameter name
Short Description
Rights
Unit / Allowed values
DI/DO Settings.OUT1 Circuit
Selection of circuit type
rw
- PushPull (default)
DI/DO Settings.OUT1 Mode
Selection of output source
(Default: SSC1)
rw
- None (SIO
deactivated)
- SSC1 (default)
- SSC4