![Baumer O200 Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/baumer/o200/o200_instruction-manual_2710746031.webp)
en_BA_O200_IO-Link_V1.docx
31/34
Baumer Electric AG
15.08.2018/
Frauenfeld, Switzerland
5.3
Dynamic (Only O200.G, O200.R)
By using the dynamic teach-in commands, it is possible to define the setpoints by evaluating the minimum
and maximum measurement values within a time frame.Accepted duration: 2 … 15 sec.
When to apply?
-
For moving and/or small objects
The command sequence to perform a dynamic teach-in is the same for all switching modes.
Command sequence:
-
Execute Dynamic
Teach Start
to start the data acquisition
-
Execute Dynamic
Teach Stop
to stop the data acquisition
-
Execute
Teach Apply
to store the setpoint
By executing
Teach Cancel
the teach-in procedure can be canceled at any state as long
Teach Apply
has not
been used.
Parameter name
Short Description
Rights
Unit /
Allowed
values
Dynamic Teach SP Start
Starts the data acquisition.
wo
Dynamic Teach SP Stop
Stops the data acquisition
wo
Teach Apply
wo
Teach Cancel
wo
5.3.1
Dynamic in Single Point Mode
If the selected SSC is configured to Single Point mode (Section 4.3.2.1), during the dynamic teach-in the
minimum and maximum values are evaluated and the setpoint SP1 set to the middle
Figure 28: Dynamic Single Point Teach, switching behavior
O200.G:
SP1 = (Min + Max) / 2
O200.R:
SP1 = sqrt(Min * Max)