en_BA_O200_IO-Link_V1.docx
12/34
Baumer Electric AG
15.08.2018/
Frauenfeld, Switzerland
4.3.2
SSC Configuration
4.3.2.1
Switching Mode
Figure 7
Single Point Mode (O200.G, O200.R)
A single setpoint (SP1) is defined at which the
sensor switches.
Figure 8
Window Mode (Only O200.G)
The sensor switches withing a range defined by two
different setpoints (SP1 and SP2)
Figure 9
Single Point Mode SmartReflect (O200.S)
A single setpoint (SP1) which represents the
position of the reference background.
Parameter name
Short Description
Rights
Unit / Allowed values
SSC1 Config.Mode
Selection of the switching mode
rw
-
Disabled
-
Single Point
-
Window
(Only O200.G)
4.3.2.2
Channel Logic
Allows to change the output logic from Normally Open (NO, Normal) to Normally closed (NC, Inverted).
Single Point Mode Window Mode
Single Point Mode Window Mode
Figure 10
«Normal» or NO setting
-
The
output is high
, when the object is
within the range defined by the setpoints.
-
The
output is low
when the object is not
present our outside of the range defined by
the setpoints
Figure 11
«Inverted» or NC setting
-
The
output is high
when the object is not
present our outside of the range defined by
the setpoints
the
output is low
, when the object is within the
range defined by the setpoints
Parameter name
Short Description
Rights
Unit / Allowed values
SSC1 Config.Logic
Changes the Logic from NO to NC
rw
-
Normal (NO)
-
Inverted (NC)