AW00101510000
Terminal Blocks and Audio Connector
Basler IP Fixed Dome Cameras
85
The functionality of each wire fixing hole in the main terminal block is as described in Table 3.
Hole Name:
Gnd (outdoor dome cameras only)
Function:
Ground for alternate camera power.
Note:
The ground for alternate camera power, the I/O ground, and the RS-485 ground are all isolated from each
other.
Hole Name:
VDC (outdoor dome cameras only)
Function:
Use this fixing hole to supply alternate power to the camera (i.e., use this connection to supply power
to the camera if you are not using PoE).
Nominal operating range: +12 to +24 VDC
Max power consumption: 10 W @ 12 VDC when the heater is enabled
5.5 W @ 12 VDC when heater is disabled
Hole Name:
Heater Off (outdoor dome cameras only)
Function:
Place a jumper between the Heater Off fixing hole and the Gnd fixing hole to disable the camera’s
heater.
If you are using alternate power, the camera’s power consumption will be 10 W when the heater is enabled and
5.5 W (@ 12 VDC) when the heater is disabled.
If you are using PoE, the camera will be Class 0 when the heater is enabled and will be Class 2 when the heater
is disabled. This can be useful when you are using the camera with a PoE switch that is only capable of
supplying low amounts of power.
Hole Name:
I/O Gnd
Function
: Ground for the camera’s I/O ports
Note:
The ground for alternate camera power, the I/O ground, and the RS-485 ground are all isolated from each
other.
Table 3: Main Terminal Block Wire Fixing Hole Assignments