APPENDIX  A  - CONE FIRE TEMPERATURE PROFILES 

 
Firing Profiles for cone 04, temperature 1945

°

F (1063

°

C) 

 

Slow Bisque 

 

 

Slow Glaze

 

Segment  Rate

°

F /hr  Temperature Stage Time Segment  Rate

°

F /hr

Temperature Stage 

Time 

3 80 250 2.25 5 150 250 1.20 
4 200 1000 3.75 6 400 1676 3.61 
5 100 1100 1.00 7 120 1926 2.08 
6 180 1676 3.31     

 

 

7 80 1926 

3.13    

 

 

13 hrs 

26 mins 

Total Time 

13.43 

6 hrs 

54 mins 

Total Time 

6.90 

 

 

 

 

Fast Bisque

 

 

 

Fast Glaze

 

Segment  Rate

°

F /hr  Temperature Stage Time Segment  Rate

°

F /hr

Temperature Stage 

Time 

3 120 250 1.50 6 570 1676 2.85 
4 300 1000 2.50 7 200 1926 1.25 
5 150 1100 0.67     

 

 

6 180 1676 3.31     

 

 

7 108 1926 2.31     

 

 

10 hrs 

17 mins 

Total Time 

10.29 

4 hrs 

6 mins 

Total Time 

4.10 

This chart shows the segments in the four cone fire speeds.  Notice that the firing profiles all end with segment 7 but they do 
not start at segment 1.  If you program a vary-fire to mimic these profiles you would start numbering with segment 1.  The 
profiles for other cone numbers are the same; only the end temperatures vary.  The last segment always starts 250

°

F below the 

cone temperature.  The actual temperature reached during the firing will vary based on the rate of temperature rise during the 
last segment.  This ensures the correct amount of heat-work is done with each cone fire program. 

APPENDIX B  -   ERROR CODES

1

 

 

Error 

Code 

Description Quick 

View 

Err0 

Software Error.  Recheck the selected program, and reprogram if 
necessary. 

If error persists, return controller for service.

 

Err1 

The temperature is increasing less than 12 degrees per hour during a 
ramp segment (in either cone fire or vary-fire mode), where the 
temperature is programmed to increase.  This slow rate must persist 
for 22.5 minutes before the error is displayed and the firing stopped.  
Pressing the "1" key clears the Err1  and briefly displays the 
temperature and then the firing time at which the error occurred. 

Ramp segment 
Temp. increase < 12

°

F/hr 

Persists > 22.5 min. 

 

Err2 

During a hold segment the temperature rises to greater than 50 
degrees above the hold temperature which was set.  The temperature 
must stay 50 

°

 above this set temperature for 18 seconds before the 

error is displayed. 

Hold segment 
> 50

°

F above set temp. 

Persists > 18 sec. 

 

Err3 

During a hold segment the temperature is more than 50 degrees 
below the hold temperature which was set. The temperature must stay 
50 

°

 below this set temperature for 18 seconds before the error is 

displayed. 

Hold segment 
> 50

°

F below set temp. 

Persists > 18 sec. 

 
 

Err4

 

The temperature is more than 50 degrees above the previous hold 
temperature during a ramp segment where the temperature is 
programmed to decrease.  The temperature must stay 50 

°

 above this 

set temperature for 18 seconds before the error is displayed. 

Decreasing Ramp segment 
> 50

°

F above last hold temp. 

Persists > 18 sec. 

                                                           

1

 Notes for Error codes.  “>” means greater than; “<” means less than; 

Содержание V6-CF

Страница 1: ...Operation Manual Model V6 CF Controller BARTLETT INSTRUMENT COMPANY 1404 Avenue M Fort Madison IA 52627 319 372 8366 WWW BARTINST COM...

Страница 2: ...reset PrHt Preheat Id identification 16 S 16 segment CnoS Cone Offset CHG Change F to C ErCd Error Codes tCoS thermocouple offset bd t board temperature and LAG Lag setting 11 ZONE CONTROL 15 1 FEATU...

Страница 3: ...to the next ramp ERROR CODES Error codes may be turned on so the kiln will automatically shut down if there is an error 16 SEGMENT PROGRAMS User 5 and 6 can be combined for a 16 segment program Messa...

Страница 4: ...firing profiles OPTIONS section for setting delay start and alarm Set one of nine Other options Default reset Preheat stage time Controller ID 16 segment program Cone offset Change F to C set Error co...

Страница 5: ...ves the traveling set point according to the programmed firing rate and recalculates how much power is needed to keep the temperature at the new traveling set point This sequence continues until the f...

Страница 6: ...amming is complete press the START STOP button to begin the firing With the display flashing IdLE alternating with the current temperature you are ready to proceed to one of the programming sections T...

Страница 7: ...temperature will be flashing in the display 8 Press START STOP to begin firing NOTE With any of the CONE FIRE modes a preheat stage is available During the preheat stage the temperature is increased a...

Страница 8: ...imal point are hours to the right of decimal point are minutes NOTE For a 1 hour hold time you could also enter 60 for 60 minutes the display would show 00 60 If you type a wrong number press zero 4 t...

Страница 9: ...y flashes between F 2 the temperature which was previously programmed 14 1 5 7 5 1575 Displays the selected temperature 15 ENTER Alternately flashing HLd2 No The displays flashes between HLd2 the prev...

Страница 10: ...segment temperature and hold time of each of the other segments will be displayed in order delay time dELA alarm setting ALAr error codes on off ErCd LAG setting if zone control View Segment only fun...

Страница 11: ...ure 2 2 0 0 0200 Displays the selected temperature of 200 If you type a wrong number press zero 4 times then type the correct number 3 ENTER CPL flashes then the current temperature CPL flashes severa...

Страница 12: ...option Press Start and the controller will fire user 5 then it will fire user 6 NOTE The first segment of user 6 must be an up ramp or the segment will be skipped CnoS Cone Offset Used to raise or low...

Страница 13: ...splayed press ENTER and the current offset for the thermocouple will be displayed Press ENTER when the correct offset is displayed The following apply to T C offsets The final temperature is affected...

Страница 14: ...des are off The current temperature then flashes in the display bd t circuit board temperature Press enter when bd t is displayed and the circuit board temperature will be displayed It is used for dia...

Страница 15: ...he sections but it will increase the firing time rSEt will set the lag to 13 Therefore anytime a section is more than 13 degrees behind the traveling set point the controller will wait for the lagging...

Страница 16: ...o 13 and error codes ErCd set to on PREHEAT PrHt CONE OFFSET CnoS CHANGE F C CHG all work as described in the OPTIONS SECTION under Programming ERRORS ON OFF ErCd also referred to as error checking wo...

Страница 17: ...ption Quick View Err0 Software Error Recheck the selected program and reprogram if necessary If error persists return controller for service Err1 The temperature is increasing less than 12 degrees per...

Страница 18: ...e fire mode only Temp decreasing during last ramp segment ErrP Continuous ErrP in display Indicates a long term power outage The kiln has been shut down Press 1 to clear the display ErrP ErrP and the...

Страница 19: ...necting the thermocouple connect the RED wire to the connector with RED dot and connect the YELLOW wire to the connector with the YELLOW dot On all thermocouples the RED wire is always negative the ye...

Страница 20: ...C 1 YELLOW OUTPUT 3 BOTTOM RED AC 1 T C2 YELLOW RED A B T C 3 YELLOW RS 485 RED OUTPUT 1 TOP 24V center tap transformer Line Voltage input Relay Top Relay Middle Relay Bottom CENTER TAP AC 2 Connect T...

Отзывы: