Err5

 

The temperature is more than 50 degrees below the travelling set-
point temperature during a ramp segment where the temperature is 
programmed to decrease.  The temperature must stay 50 

°

 below this 

set temperature for 18 seconds before the error is displayed. 

Decreasing Ramp segment 
> 50

°

F below travelling set-point temp. 

Persists > 18 sec. 

 
 
 

Err6

 

A Negative temperature is detected.  This generally  indicates the 
thermocouple is connected incorrectly.  To correct this situation, 
ensure the red and yellow wires are connected correctly to the 
controller and at all t/c junctions.  You can identify the red lead on an 
unmarked thermocouple with a magnet because a magnet will be 
attracted to the red lead. 

(-) displayed 

 

Err7

 

The temperature is more than 50 degrees above the travelling set-
point temperature during a ramp segment where the temperature is 
programmed to increase.  The temperature must stay 50 

°

 above this 

set temperature for 18 seconds before the error is displayed. 

Increasing Ramp segment 
> 50

°

F above travelling set-point temp. 

Persists > 18 sec. 

 

Err8 

When using the Cone Fire Mode, the temperature is decreasing 
during the last ramp segment indicating the a kiln sitter or timer may 
have turned the kiln off or an element or relay failed during the last 
segment. 

Cone fire mode only 
Temp. decreasing during last ramp segment 

ErrP

 

 

Continuous ErrP in display.  Indicates a long term power outage.  
The kiln has been shut down.  Press “1” to clear the display. 

 

 

ErrP

 

 

ErrP and the current temperature are alternately flashing.  To clear 
the display, press the “1” key.  If a firing was in progress, it will 
continue. 

 

Err- 

The Err with a dash indicates there was a power loss to the controller 
while writing a program to the non-volatile memory chip.   

Turn the controller off and back on. 
Recheck the selected program, and 
reprogram if necessary. 

ErrE 

or 

Errt 

The controller software has detected a hardware error.  The controller 
must be returned for service. 

Hardware error 

 

Errd 

The kiln temperature is more than 100

°

F above the travelling set-

point.  If a zone control then any one of the zone temperatures is 
more than 100 degrees F above the travelling set point. 

Can be caused by a stuck relay or stuck 
output.  If zone control, then the outputs or 
t/c's may be in the wrong zones 

 

ErrA 

Invalid program variable.   

Reprogram; if problem persists return board 
for service 
 

 

StUc 

Key was held too long or is stuck 

If problem persists after releasing key have 
key pad replaced 

 
 

FAIL 

Steady FAIL display then all thermocouples (t/c) have failed.  If tC 1 
alternately flashing with FAIL then t/c one in top section has failed. 
tC 2 flashing with FAIL, then t/c 2 (middle section) has failed.  tC 3 
flashing with FAIL, then t/c 3 (bottom section) has failed. 

Change thermocouple (t/c) 

 

 

Содержание V6-CF

Страница 1: ...Operation Manual Model V6 CF Controller BARTLETT INSTRUMENT COMPANY 1404 Avenue M Fort Madison IA 52627 319 372 8366 WWW BARTINST COM...

Страница 2: ...reset PrHt Preheat Id identification 16 S 16 segment CnoS Cone Offset CHG Change F to C ErCd Error Codes tCoS thermocouple offset bd t board temperature and LAG Lag setting 11 ZONE CONTROL 15 1 FEATU...

Страница 3: ...to the next ramp ERROR CODES Error codes may be turned on so the kiln will automatically shut down if there is an error 16 SEGMENT PROGRAMS User 5 and 6 can be combined for a 16 segment program Messa...

Страница 4: ...firing profiles OPTIONS section for setting delay start and alarm Set one of nine Other options Default reset Preheat stage time Controller ID 16 segment program Cone offset Change F to C set Error co...

Страница 5: ...ves the traveling set point according to the programmed firing rate and recalculates how much power is needed to keep the temperature at the new traveling set point This sequence continues until the f...

Страница 6: ...amming is complete press the START STOP button to begin the firing With the display flashing IdLE alternating with the current temperature you are ready to proceed to one of the programming sections T...

Страница 7: ...temperature will be flashing in the display 8 Press START STOP to begin firing NOTE With any of the CONE FIRE modes a preheat stage is available During the preheat stage the temperature is increased a...

Страница 8: ...imal point are hours to the right of decimal point are minutes NOTE For a 1 hour hold time you could also enter 60 for 60 minutes the display would show 00 60 If you type a wrong number press zero 4 t...

Страница 9: ...y flashes between F 2 the temperature which was previously programmed 14 1 5 7 5 1575 Displays the selected temperature 15 ENTER Alternately flashing HLd2 No The displays flashes between HLd2 the prev...

Страница 10: ...segment temperature and hold time of each of the other segments will be displayed in order delay time dELA alarm setting ALAr error codes on off ErCd LAG setting if zone control View Segment only fun...

Страница 11: ...ure 2 2 0 0 0200 Displays the selected temperature of 200 If you type a wrong number press zero 4 times then type the correct number 3 ENTER CPL flashes then the current temperature CPL flashes severa...

Страница 12: ...option Press Start and the controller will fire user 5 then it will fire user 6 NOTE The first segment of user 6 must be an up ramp or the segment will be skipped CnoS Cone Offset Used to raise or low...

Страница 13: ...splayed press ENTER and the current offset for the thermocouple will be displayed Press ENTER when the correct offset is displayed The following apply to T C offsets The final temperature is affected...

Страница 14: ...des are off The current temperature then flashes in the display bd t circuit board temperature Press enter when bd t is displayed and the circuit board temperature will be displayed It is used for dia...

Страница 15: ...he sections but it will increase the firing time rSEt will set the lag to 13 Therefore anytime a section is more than 13 degrees behind the traveling set point the controller will wait for the lagging...

Страница 16: ...o 13 and error codes ErCd set to on PREHEAT PrHt CONE OFFSET CnoS CHANGE F C CHG all work as described in the OPTIONS SECTION under Programming ERRORS ON OFF ErCd also referred to as error checking wo...

Страница 17: ...ption Quick View Err0 Software Error Recheck the selected program and reprogram if necessary If error persists return controller for service Err1 The temperature is increasing less than 12 degrees per...

Страница 18: ...e fire mode only Temp decreasing during last ramp segment ErrP Continuous ErrP in display Indicates a long term power outage The kiln has been shut down Press 1 to clear the display ErrP ErrP and the...

Страница 19: ...necting the thermocouple connect the RED wire to the connector with RED dot and connect the YELLOW wire to the connector with the YELLOW dot On all thermocouples the RED wire is always negative the ye...

Страница 20: ...C 1 YELLOW OUTPUT 3 BOTTOM RED AC 1 T C2 YELLOW RED A B T C 3 YELLOW RS 485 RED OUTPUT 1 TOP 24V center tap transformer Line Voltage input Relay Top Relay Middle Relay Bottom CENTER TAP AC 2 Connect T...

Отзывы: