A 1/4 inch clearance to combustible material for the first
three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures 3
and 3A for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.  A
metallic return air grille is required with installations not
requiring a return air duct.  The spacing between louvers
on the grille shall not be larger than 5/8 inch.

NOTE:  If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

Any grille that meets with 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used.  Contact distributor or
factory for ordering information.  If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top
of the unit down to the unit base.  There are openings in
the unit base for the drain hose to pass through.  In the
event the drain hose is connected to a drain system of
some type, it must be an open or vented type system to
assure proper drainage.

FILTERS

WA6022 AND WA4822 ONLY

A one inch throw away filter is supplied with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A one inch washable filter and a two
inch pleated filter are also available as optional
accessories.  The internal filter brackets are adjustable to
accommodate the two inch filter by bending the metal
tabs holding the 1 inch filter down.  There are two tabs
on each side of the filter.

NOTE: WA6023 and WA4823 models require the use of

a return air filter grille.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 1 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment.  Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked
for external signs of shipping damage.  If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly any tags and/
or labels attached to the equipment.

Содержание WA4822

Страница 1: ...PACKAGE AIR CONDITIONERS MODELS WA4822 WA4823 WA6022 WA6023 WA602N Manual 2100 348D Supersedes 2100 348C File Volume III Tab 16 Date 05 20 01 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 2001 ...

Страница 2: ...nt Charge 17 Table 8 Rated CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall Mount Model Nomenclature 2 Shipping Damage 6 General 6 Duct Work 6 Condensate Drain 6 Filters 6 Installation Instructions 7 Wall Mounting...

Страница 3: ... Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Society of...

Страница 4: ...0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS B Blank off Plate FILTER OPTIONS N No Filter WA4823 WA6023 WA602N models ONLY X One Inch Throwaway Filter WA4822 WA6022 models ONLY W One Inch Washable Filter WA4822 WA6022 models ONLY P Two Inch Pleated Filter WA4822 WA6022 models ONLY COLO...

Страница 5: ...Manual 2100 348 Page 3 FIGURE 1 UNIT DIMENSIONS WA602N WA6023 WA4823 ONLY MIS 1348 ...

Страница 6: ...Manual 2100 348 Page 4 FIGURE 2 UNIT DIMENSIONS WA6022 WA4822 ONLY MIS 1442 ...

Страница 7: ...T K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 2 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 2 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 3 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 3 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 2 2 0 ...

Страница 8: ...ch filter by bending the metal tabs holding the 1 inch filter down There are two tabs on each side of the filter NOTE WA6023 and WA4823 models require the use of a return air filter grille While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation i...

Страница 9: ...upply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WARNING Fai...

Страница 10: ...Manual 2100 348 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WA602N WA6023 WA4823 ONLY MIS 1349 ...

Страница 11: ...Manual 2100 348 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WA6022 WA4822 ONLY MIS 1444 ...

Страница 12: ...WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death ...

Страница 13: ...ALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED WALL OVER FRAME 1 000 CLEARANCE ALL AROUND EXTERIOR FINISHED WALL OVER FRAME ATTACH TO BOTTOM PLATE OF WALL FRAMING MATERIAL 2 X 4 S 2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED T...

Страница 14: ...Manual 2100 348 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550 ...

Страница 15: ...Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in Figure 9 See Start Up section for important information on three phase scroll compressor start ups WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers A...

Страница 16: ...Manual 2100 348 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS 1373A ...

Страница 17: ...installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two line connections to the unit SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air registers This reduces air flow throu...

Страница 18: ...amage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage m...

Страница 19: ...ABLE 6 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 O N 2 0 6 A W 3 2 0 6 A W 2 2 0 6 A W 3 2 8 4 A W 2 2 8 4 A W d e e p S h g i H d e e p S h g i H d e e p S h g i H d e e p S h g i H y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 0 5 8 1 5 5 7 1 0 0 7 1 5 7 6 1 0 0 6 1 5 2 ...

Страница 20: ...5 2 9 7 9 6 2 0 8 5 8 2 1 8 3 0 3 2 8 1 2 3 3 8 0 4 3 4 8 0 6 3 5 8 1 8 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 4 8 5 4 2 5 8 1 6 2 5 8 8 7 2 6 8 6 9 2 7 8 4 1 3 8 8 3 3 3 9 8 3 5 3 0 9 3 7 3 1 9 4 9 3 2 8 4 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 4 0 2 4 7 7 1 2 6 7 2 3 2 8 7 8 4 2 9 7 5 6 2 0 8 4 8 2 2 8 4 0 3 3 8 5 2 3 4 8 8 4 3 B D g e d 0 8 B W g ...

Страница 21: ...WA4822A WA4823B WA4822B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C X X X X ...

Отзывы: