Manual   2100-348
Page    15

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil
with a dish washing detergent.

CRANKCASE HEATERS

These units are not provided with crankcase heat.  These
units utilize scroll compressors which do not require
crankcase heat in this application.

HIGH PRESSURE SWITCH

The models are supplied with a remote reset high
pressure switch. If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with single
phase compressors since they will always start and run in
the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the time
the equipment is put into service. If improper rotation is
corrected at this time there will be no negative impact on
the durability of the compressor. However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor’s
internal protector will trip.

All three phase ZR3 compressors are wired identically
internally. As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation direction.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times. Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch. Turn thermostat off then
on to reset the high pressure switch.

3. Check all power fuses or circuit breakers to be sure

they are the correct rating.

4. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling in

compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling operation
or can be energized by manual fan switch on subbase of
constant air circulation.  On all 230 volt units there is a
one minute off delay on the blower motor.  460 volt
models do not have an off delay.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on the models
covered by this manual.  The compressor control is an
anti-short cycle/lockout timer with high and low pressure
switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit  the delay on make period begins which will be 2
minutes plus 10% of the delay on break setting.  When
the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.

Содержание WA4822

Страница 1: ...PACKAGE AIR CONDITIONERS MODELS WA4822 WA4823 WA6022 WA6023 WA602N Manual 2100 348D Supersedes 2100 348C File Volume III Tab 16 Date 05 20 01 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 2001 ...

Страница 2: ...nt Charge 17 Table 8 Rated CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall Mount Model Nomenclature 2 Shipping Damage 6 General 6 Duct Work 6 Condensate Drain 6 Filters 6 Installation Instructions 7 Wall Mounting...

Страница 3: ... Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Society of...

Страница 4: ...0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS B Blank off Plate FILTER OPTIONS N No Filter WA4823 WA6023 WA602N models ONLY X One Inch Throwaway Filter WA4822 WA6022 models ONLY W One Inch Washable Filter WA4822 WA6022 models ONLY P Two Inch Pleated Filter WA4822 WA6022 models ONLY COLO...

Страница 5: ...Manual 2100 348 Page 3 FIGURE 1 UNIT DIMENSIONS WA602N WA6023 WA4823 ONLY MIS 1348 ...

Страница 6: ...Manual 2100 348 Page 4 FIGURE 2 UNIT DIMENSIONS WA6022 WA4822 ONLY MIS 1442 ...

Страница 7: ...T K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 2 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 2 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 3 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 3 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 2 2 0 ...

Страница 8: ...ch filter by bending the metal tabs holding the 1 inch filter down There are two tabs on each side of the filter NOTE WA6023 and WA4823 models require the use of a return air filter grille While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation i...

Страница 9: ...upply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WARNING Fai...

Страница 10: ...Manual 2100 348 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WA602N WA6023 WA4823 ONLY MIS 1349 ...

Страница 11: ...Manual 2100 348 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WA6022 WA4822 ONLY MIS 1444 ...

Страница 12: ...WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death ...

Страница 13: ...ALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED WALL OVER FRAME 1 000 CLEARANCE ALL AROUND EXTERIOR FINISHED WALL OVER FRAME ATTACH TO BOTTOM PLATE OF WALL FRAMING MATERIAL 2 X 4 S 2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED T...

Страница 14: ...Manual 2100 348 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550 ...

Страница 15: ...Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in Figure 9 See Start Up section for important information on three phase scroll compressor start ups WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers A...

Страница 16: ...Manual 2100 348 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS 1373A ...

Страница 17: ...installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two line connections to the unit SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air registers This reduces air flow throu...

Страница 18: ...amage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage m...

Страница 19: ...ABLE 6 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 O N 2 0 6 A W 3 2 0 6 A W 2 2 0 6 A W 3 2 8 4 A W 2 2 8 4 A W d e e p S h g i H d e e p S h g i H d e e p S h g i H d e e p S h g i H y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 0 5 8 1 5 5 7 1 0 0 7 1 5 7 6 1 0 0 6 1 5 2 ...

Страница 20: ...5 2 9 7 9 6 2 0 8 5 8 2 1 8 3 0 3 2 8 1 2 3 3 8 0 4 3 4 8 0 6 3 5 8 1 8 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 4 8 5 4 2 5 8 1 6 2 5 8 8 7 2 6 8 6 9 2 7 8 4 1 3 8 8 3 3 3 9 8 3 5 3 0 9 3 7 3 1 9 4 9 3 2 8 4 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 4 0 2 4 7 7 1 2 6 7 2 3 2 8 7 8 4 2 9 7 5 6 2 0 8 4 8 2 2 8 4 0 3 3 8 5 2 3 4 8 8 4 3 B D g e d 0 8 B W g ...

Страница 21: ...WA4822A WA4823B WA4822B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C X X X X ...

Отзывы: