INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings must

be cut through the wall as shown in Figure 1 or 2.
Figure 1 is for models WA4823, and WA6023.
Figure 2 is for Models WA4822 and WA6022.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the unit
without transmitting any unit vibration.

       WARING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained.  See Figure 3.

3. Concrete block walls must be thoroughly inspected to

insure that they are capable of carrying the weight of
the installed unit.

WA4822 AND WA6022 ONLY

These units are equipped with adjustable return and
supply air flanges.  The flanges are adjustable side to side
in 1” increments.  This allows these units to be adjusted
so that in side by side applications these units can replace
two 2 Ton units using the same wall openings.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but the

supply air duct flange and the first 3 feet of supply air
duct require a minimum of 1/4 inch clearance to
combustible material.  If a combustible wall use a
minimum of 30-1/2” x 10-1/2” dimensions for sizing.
However it is generally recommended that a 1 inch
clearance is used for ease of installation and
maintaining the required clearance to combustible
material.  The supply air opening would then be 32” x
12”.  See Figures 2 and 3 for details.

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 2.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of the
back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 2.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side by side installations, maintain a minimum of

20 inches clearance on right side to allow access to
control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance may
be required to meet local or national codes.

Содержание WA4822

Страница 1: ...PACKAGE AIR CONDITIONERS MODELS WA4822 WA4823 WA6022 WA6023 WA602N Manual 2100 348D Supersedes 2100 348C File Volume III Tab 16 Date 05 20 01 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 2001 ...

Страница 2: ...nt Charge 17 Table 8 Rated CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall Mount Model Nomenclature 2 Shipping Damage 6 General 6 Duct Work 6 Condensate Drain 6 Filters 6 Installation Instructions 7 Wall Mounting...

Страница 3: ... Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Society of...

Страница 4: ...0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS B Blank off Plate FILTER OPTIONS N No Filter WA4823 WA6023 WA602N models ONLY X One Inch Throwaway Filter WA4822 WA6022 models ONLY W One Inch Washable Filter WA4822 WA6022 models ONLY P Two Inch Pleated Filter WA4822 WA6022 models ONLY COLO...

Страница 5: ...Manual 2100 348 Page 3 FIGURE 1 UNIT DIMENSIONS WA602N WA6023 WA4823 ONLY MIS 1348 ...

Страница 6: ...Manual 2100 348 Page 4 FIGURE 2 UNIT DIMENSIONS WA6022 WA4822 ONLY MIS 1442 ...

Страница 7: ...T K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 2 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 2 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 3 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 3 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 2 2 0 ...

Страница 8: ...ch filter by bending the metal tabs holding the 1 inch filter down There are two tabs on each side of the filter NOTE WA6023 and WA4823 models require the use of a return air filter grille While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation i...

Страница 9: ...upply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WARNING Fai...

Страница 10: ...Manual 2100 348 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WA602N WA6023 WA4823 ONLY MIS 1349 ...

Страница 11: ...Manual 2100 348 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WA6022 WA4822 ONLY MIS 1444 ...

Страница 12: ...WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death ...

Страница 13: ...ALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED WALL OVER FRAME 1 000 CLEARANCE ALL AROUND EXTERIOR FINISHED WALL OVER FRAME ATTACH TO BOTTOM PLATE OF WALL FRAMING MATERIAL 2 X 4 S 2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED T...

Страница 14: ...Manual 2100 348 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550 ...

Страница 15: ...Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in Figure 9 See Start Up section for important information on three phase scroll compressor start ups WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers A...

Страница 16: ...Manual 2100 348 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS 1373A ...

Страница 17: ...installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two line connections to the unit SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air registers This reduces air flow throu...

Страница 18: ...amage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage m...

Страница 19: ...ABLE 6 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 O N 2 0 6 A W 3 2 0 6 A W 2 2 0 6 A W 3 2 8 4 A W 2 2 8 4 A W d e e p S h g i H d e e p S h g i H d e e p S h g i H d e e p S h g i H y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 0 5 8 1 5 5 7 1 0 0 7 1 5 7 6 1 0 0 6 1 5 2 ...

Страница 20: ...5 2 9 7 9 6 2 0 8 5 8 2 1 8 3 0 3 2 8 1 2 3 3 8 0 4 3 4 8 0 6 3 5 8 1 8 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 4 8 5 4 2 5 8 1 6 2 5 8 8 7 2 6 8 6 9 2 7 8 4 1 3 8 8 3 3 3 9 8 3 5 3 0 9 3 7 3 1 9 4 9 3 2 8 4 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 4 0 2 4 7 7 1 2 6 7 2 3 2 8 7 8 4 2 9 7 5 6 2 0 8 4 8 2 2 8 4 0 3 3 8 5 2 3 4 8 8 4 3 B D g e d 0 8 B W g ...

Страница 21: ...WA4822A WA4823B WA4822B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C X X X X ...

Отзывы: