PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models. It is imperative to match the
correct pressure table to the unit by model number.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor and
phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch
opens again in this same operating cycle the unit will
go into manual lockout condition and the alarm relay
circuit will energize.   Recycling the wall thermostat
resets the manual lockout.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is equal
to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds.

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds.

Содержание WA4822

Страница 1: ...PACKAGE AIR CONDITIONERS MODELS WA4822 WA4823 WA6022 WA6023 WA602N Manual 2100 348D Supersedes 2100 348C File Volume III Tab 16 Date 05 20 01 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 2001 ...

Страница 2: ...nt Charge 17 Table 8 Rated CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall Mount Model Nomenclature 2 Shipping Damage 6 General 6 Duct Work 6 Condensate Drain 6 Filters 6 Installation Instructions 7 Wall Mounting...

Страница 3: ... Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Society of...

Страница 4: ...0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS B Blank off Plate FILTER OPTIONS N No Filter WA4823 WA6023 WA602N models ONLY X One Inch Throwaway Filter WA4822 WA6022 models ONLY W One Inch Washable Filter WA4822 WA6022 models ONLY P Two Inch Pleated Filter WA4822 WA6022 models ONLY COLO...

Страница 5: ...Manual 2100 348 Page 3 FIGURE 1 UNIT DIMENSIONS WA602N WA6023 WA4823 ONLY MIS 1348 ...

Страница 6: ...Manual 2100 348 Page 4 FIGURE 2 UNIT DIMENSIONS WA6022 WA4822 ONLY MIS 1442 ...

Страница 7: ...T K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 2 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 2 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 3 2 8 4 A W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 3 2 8 4 A W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N A N A N Z 0 A 0 0 A 2 2 0 ...

Страница 8: ...ch filter by bending the metal tabs holding the 1 inch filter down There are two tabs on each side of the filter NOTE WA6023 and WA4823 models require the use of a return air filter grille While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation i...

Страница 9: ...upply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WARNING Fai...

Страница 10: ...Manual 2100 348 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WA602N WA6023 WA4823 ONLY MIS 1349 ...

Страница 11: ...Manual 2100 348 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WA6022 WA4822 ONLY MIS 1444 ...

Страница 12: ...WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death ...

Страница 13: ...ALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED WALL OVER FRAME 1 000 CLEARANCE ALL AROUND EXTERIOR FINISHED WALL OVER FRAME ATTACH TO BOTTOM PLATE OF WALL FRAMING MATERIAL 2 X 4 S 2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED T...

Страница 14: ...Manual 2100 348 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550 ...

Страница 15: ...Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in Figure 9 See Start Up section for important information on three phase scroll compressor start ups WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers A...

Страница 16: ...Manual 2100 348 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS 1373A ...

Страница 17: ...installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two line connections to the unit SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air registers This reduces air flow throu...

Страница 18: ...amage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage m...

Страница 19: ...ABLE 6 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 O N 2 0 6 A W 3 2 0 6 A W 2 2 0 6 A W 3 2 8 4 A W 2 2 8 4 A W d e e p S h g i H d e e p S h g i H d e e p S h g i H d e e p S h g i H y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 0 5 8 1 5 5 7 1 0 0 7 1 5 7 6 1 0 0 6 1 5 2 ...

Страница 20: ...5 2 9 7 9 6 2 0 8 5 8 2 1 8 3 0 3 2 8 1 2 3 3 8 0 4 3 4 8 0 6 3 5 8 1 8 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 4 8 5 4 2 5 8 1 6 2 5 8 8 7 2 6 8 6 9 2 7 8 4 1 3 8 8 3 3 3 9 8 3 5 3 0 9 3 7 3 1 9 4 9 3 2 8 4 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 4 0 2 4 7 7 1 2 6 7 2 3 2 8 7 8 4 2 9 7 5 6 2 0 8 4 8 2 2 8 4 0 3 3 8 5 2 3 4 8 8 4 3 B D g e d 0 8 B W g ...

Страница 21: ...WA4822A WA4823B WA4822B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C X X X X ...

Отзывы: