background image

Manual 2100-703H 

Page 

7 of 42

Fire hazard.

Maintain minimum 1/4" clearance between the 
supply air duct and combustible materials in 

the first 3' of ducting.
Failure to do so could result in fire causing 

damage, injury or death.

!

WARNING

directly in front of the unit return grilles and registers. 
Bard recommends at least 2' between solid objects 
and return grilles or registers. Ductwork may be used to 
ensure proper air circulation and all provided ductwork 
guidelines and clearances must be followed. Non-
ducted applications must use a return louver grille 
installed over the return opening inside the room. 

Ducted Applications

Field fabricated supply and return duct work may be 
installed inside the structure being conditioned. A short 
supply and/or return stub duct may be connected to the 
unit supply and return flanges before unit installation to 
help with duct connections inside the structure. Supply 
and return ducts must be properly sized for the design 
airflow requirement of the equipment. Air Conditioning 
Contractors of America (ACCA) is an excellent guide 
to proper sizing. All duct work or portions thereof not 
in the conditioned space should be properly insulated 
in order to conserve energy, reduce heat conductivity, 
and prevent condensation or moisture damage. Refer to 
Maximum External Static Pressure (ESP) of Operation 
Table 17 on page 38. Design the duct work according 
to methods given by the Air Conditioning Contractors 
of America (ACCA). When duct work is installed 
in unheated spaces, it should be insulated with a 
minimum of 1" of insulation. Use insulation with a 
vapor barrier on the outside of the insulation. Flexible 
joints should be used to connect the duct work to the 
equipment in order to keep the noise transmission to a 
minimum. Ducts through the walls must be insulated 
and all joints taped or sealed to prevent air or moisture 
from entering the wall cavity.
The unit itself is suitable for 0" clearance, but the 
supply air duct flange and the first 3' of supply air duct 
require a minimum of 1/4" clearance to combustible 
material for model series W30 and W36. However, it 
is generally recommended that a 1" clearance is used 
for ease of installation and maintaining the required 
clearance to combustible material. See Figures 3A and 
3B on pages 10 and 11 for details on opening sizes.

Free Blow Applications

Some installations may not require extensive supply 
duct work throughout the structure and are referred 
to as free blow applications. A short field-fabricated 
supply duct must be used in the wall cavity to 
transition between the supply collar on the unit and 
the supply louver grille in the room. The duct must 
be properly insulated in order to conserve energy, 
reduce heat conductivity and prevent condensation or 
moisture damage. All joints must be taped or sealed to 
prevent air or moisture entering the wall cavity. Follow 
all clearances including distances to combustible 
materials and all instructions provided in this manual. 
A non-restrictive metallic supply air grille with 
deflectors is required for free blow applications. Contact 
the local Bard distributor or visit www.bardhvac.com for 
ordering information.
A metallic return air grille is required for non-ducted 
applications. The spacing between louvers on the grille 
shall not be larger than 5/8". It is recommended that a 
Bard Return Air Grille Kit be installed that is designed 
specifically for the wall mount product. Contact the 
local Bard distributor or visit www.bardhvac.com for 
ordering information. A field-supplied return grille 
that meets the 5/8" louver criteria and does not cause 
the unit to exceed the maximum specified external 
static pressure (ESP) may be used. If using a return 
air filter grille, filters must be of sufficient size to 
allow a maximum velocity of 400 fpm. Filter return 
air grilles do not filter air being brought into the 
structure through ventilation options including fresh air 
dampers, ventilators, economizers and energy recovery 
ventilators. Be sure to install the return grille with the 
louvers pointed downward towards the floor. This will 
help ensure return air is drawn upward from the floor 
and improve air circulation in the room.

NOTE:

  If no return air duct is used, applicable 

installation codes may limit this cabinet to 

installation only in a single story structure.

Thermostat or Indoor Temperature Sensor Placement

The location and installation of the thermostat or 
temperature sensor that monitors indoor temperature is 
very important regarding unit operation. Avoid placing 
the thermostat in an area exposed to direct sunlight 
or air from doorways leading outdoors. Use a piece 
of insulating material to close off conduit openings 
or holes in the wall surface for wire entry into the 
thermostat or temperature sensor. This will help avoid 
non-conditioned air from entering the thermostat 
and effecting temperature and/or humidity readings. 
As common practice, the thermostat or temperature 
sensor should measure the temperature of the air 
being returned to the unit, and not the conditioned 
air being supplied by the unit. Placing the thermostat 
or temperature sensor near a return air opening will 
normally result in optimal unit performance.

Содержание W30HB Series

Страница 1: ...IONS W18HB A W24HB A W24HB B W24HB C W30HB A W30HB B W30HB C W36HB A W36HB B W36HB C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 703H Supersedes 2100 703G Date 3 1 21...

Страница 2: ...tallation 8 Materials Tool List 8 Wall Preparation 8 Wall Mount Installation to Wall Surface 8 Wiring Main Power 15 Wiring Low Voltage 15 Low Voltage Connections 15 Unit Shutdown Feature 15 Balanced C...

Страница 3: ...tallation ANSI NFPA 90A of Air Conditioning and Ventilating Systems Standard for Warm Air ANSI NFPA 90B Heating and Air Conditioning Systems Load Calculation for ACCA Manual J Residential Winter and S...

Страница 4: ...on of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a va...

Страница 5: ...utor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable ins...

Страница 6: ...ensate removal from the outdoor coil when in heating mode The unit must be mounted high enough above grade to ensure that ice will not build up under the unit and come into contact with the base of th...

Страница 7: ...upply duct must be used in the wall cavity to transition between the supply collar on the unit and the supply louver grille in the room The duct must be properly insulated in order to conserve energy...

Страница 8: ...hind the unit that is against the wall A bottom mounting bracket attached to the skid for shipping is provided for ease of installation but is not required Review all requirements listed on unit label...

Страница 9: ...er Access Panel Standard flush vent door for non ERV Econ models 1 Ventilation Air F W 5 88 G All dimensions are in inches Dimensional drawings are not to scale TABLE 1 Clearance Required for Service...

Страница 10: ...NG AT TIME OF INSTALLATION OPENING MIS 3157 A ENTIRE LENGTH OF TOP TOP NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND IS...

Страница 11: ...SHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS DUCT RETURN AIR Right Side View SEAL WI...

Страница 12: ...aintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 of ducting Failure to do so could result in fire causing damage injury or death WARNING SIDE SECTION...

Страница 13: ...NIT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...ed to an external NC normally closed contact such as a fire smoke detector that will cause shutdown of the equipment upon activation Electrical shock hazard Do not operate this equipment without an ea...

Страница 16: ...o control dehumidification operation Ventilation Features Optional See ventilation instructions provided with unit for low voltage wiring Low Ambient Control LAC The low ambient control is a pressure...

Страница 17: ...igent Learning Control BACnet compatible Ethernet compatible 8403 095 T4 Pro 1 stage Cool 2 stage Heat Heat Pump 1 stage Cool 1 stage Heat Conventional Programmable Non Programmable Electronic Auto or...

Страница 18: ...used 6 control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 5 8 and fan set to be programmed fan for the A output to function d...

Страница 19: ...n add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See install manual 4 Factory installed jumper Remove ju...

Страница 20: ...or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control p...

Страница 21: ...dition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur Condenser Fan Operation NOTE Certain models may be equipped with a low ambien...

Страница 22: ...ot gas passing through the outdoor coil melts any accumulated frost When the temperature rises to approximately 57 F the coil temperature sensor will send a signal to the heat pump control which will...

Страница 23: ...nd there is no Y1 at the compressor control module first check to make sure that either the optional vent is plugged into the vent connection plug or the supplied jumper plug is in place The unit will...

Страница 24: ...rol Board 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN...

Страница 25: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 26: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 27: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Страница 28: ...failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The SelecTech...

Страница 29: ...refrigerant charge quantity The pressure tables on the following pages show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informati...

Страница 30: ...150 414 152 440 154 467 156 495 157 524 159 554 161 585 162 618 TABLE 11B Heating Pressure Air Temperature Entering Outdoor Coil F Model Indoor Heating 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 W1...

Страница 31: ...85 72 Low Side High Side 125 302 131 327 136 352 141 377 145 403 148 430 151 458 153 486 154 514 155 543 155 573 155 609 W24HB 75 62 Low Side High Side 116 294 118 314 121 336 123 359 125 382 127 406...

Страница 32: ...14 12 10 These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electrical code latest version Article 310 for power conductor sizing CAUTION...

Страница 33: ...ult W24HB 800 10 700 950 W30HB 1000 15 900 1125 W36HB 1100 15 1000 1200 Rated CFM and ESP on factory speed connection NOTE Be sure to adjust the system static or blower speed to maintain airflows abov...

Страница 34: ...Cooling X X X X Balanced Climate On Full Load Cool X X X X X X Lo Med Hi On Balanced Climate Heat Pump Heating X X X X X Balanced Climate On Full Load Heat Pump Heating X X X X X X X Lo Med Hi On 1st...

Страница 35: ...justment 1 Apply power to the unit 2 Turn the unit indoor blower on energize R G on low voltage terminal board 3 With air filters installed and switch initially set at 0 4 W C see Step 2 under Dirty F...

Страница 36: ...2100 703H Page 36 of 42 FIGURE 17 Adjusting Dirty Filter Switch TURN CLOCKWISE TO INCREASE RESTRICTION AMOUNT REQUIRED TO ACTIVATE THE SWITCH AND COUNTER CLOCKWISE TO DECREASE RESTRICTION AMOUNT MIS...

Страница 37: ...01 793 778 915 898 1040 1014 0 25 777 761 899 878 1017 981 0 30 758 742 880 856 988 944 0 40 716 701 831 806 912 860 0 50 664 655 767 747 814 761 W30HB 0 00 856 823 1083 1063 Dedicated electric heat s...

Страница 38: ...Speed W30H W36H A00 0Z A05 A10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 0Z B05 B09 50 40 30 50 50 35 W30H W36H C00 0Z C05 C09 50 40 30 50 50 40 Models 240V 1 208V 1 240V 3 208V 3 460V 3 KW Amps BTUH...

Страница 39: ...EHW18H A04 X EHW18H A08 X EHW2HB A04 X EHW2HB A08 X EHW2HB B05 X EHW2HB C05 X EHW3HB A05 X EHW3HB A10 X EHW3HB A15 X EHW3HB B05 X EHW3HB B09 X X EHW3HB C05 X X EHW3HB C09 X X EHW30HB A05 X EHW30HB A10...

Страница 40: ...X SK 111 Start Kit Hard Start X X X BOP2 Blank Off Plate X X FAD NE2 Fresh Air Damper No Exhaust X X FAD BE2 Fresh Air Damper Barometric Exhaust X X CRV F2 Commercial Ventilator On Off Spring Return X...

Страница 41: ...Manual 2100 703H Page 41 of 42 GRAPH 1 W18HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 W24HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Страница 42: ...Manual 2100 703H Page 42 of 42 GRAPH 3 W30HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 W36HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Отзывы: