background image

Manual 2100-703H 

Page 

16 of 42

Balanced Climate™ Feature (Standard on All Models)

All units are equipped with the capability of running 
in Balanced Climate mode. This mode is designed to 
enhance the comfort level by reducing the indoor airflow 
amount and extending the run time to help extract 
more humidity during cooling operation. In heating 
mode, the reduced airflow provides a warmer supply 
air temperature creating more comfortable heat. The 
Y1 terminal is the 24VAC input for Balanced Climate 
compressor cooling operation. The Y2 terminal is the 
24VAC input for compressor cooling standard operation. 
Y1 and Y2 are connected with a brass jumper bar which 
can be removed to enable Balanced Climate mode. 
Units with an economizer will not have the brass jumper 
installed. Refer to vent manuals for instructions on how 
Balanced Climate works with each vent.

NOTE:

  Units with mechanical dehumidification 

require an additional connection to be made 

when enabling Balanced Climate. Refer to 

dehumidification supplemental instructions for 

this step.

 

To operate in Balanced Climate mode, a 2-stage cooling 
thermostat is required. The lower indoor airflow operation 
is overridden by utilizing a 2-stage thermostat. If the call 
for cooling is not satisfied within a given time frame or 
temperature differential (specified by the thermostat), 
the thermostat will send a signal to Y2 which then 
increases the blower speed back to the selected speed. 
See pages 33 – 34 for blower speed selection options. 

Refer to page 21 for additional Balanced Climate 

requirements and limitations.

Dehumidification Feature (Optional) 

The D terminal is the 24VAC input for dehumidification 
operation on dehumidification hot gas reheat equipped 
units. When 24VAC is applied to the D terminal, a 
3-way valve solenoid is energized. The reheat coil 
located behind the evaporator coil is then active to 
reheat the supply air during cooling mode. This allows 
humidity to be removed from the air entering the unit 
without a large amount of sensible cooling capacity. 
During dehumidification, the indoor blower speed is 
reduced to help with the humidity removal. A humidity 
sensing thermostat or humidistat is required to control 
dehumidification operation.

Ventilation Features (Optional) 

See ventilation instructions provided with unit for low 
voltage wiring.

Low Ambient Control (LAC)

The low ambient control is a pressure switch that is 
attached to the liquid line of the system and monitors 
high side pressure. Operation of the LAC occurs as 
outdoor temperatures drop below 60°F. On/Off and 
modulating controls are used which operate based 
on pressure changes caused by outdoor temperature 

Standard Units

Units w/

Economizers

Fan Only

Energize G

Energize G

1st Stage 
Cooling Mode/
Balanced Climate

Energize Y1, G

Energize Y1, G

2nd Stage 
Cooling Mode

Energize Y2 
to override 
Balanced Climate 
mode when 
Y1-Y2 jumper is 
removed

Energize Y1, Y2, G

1st Stage Heating

Energize Y1, B/W1

Energize Y1, B/W1

2nd Stage Heating

(if employed)

Energize Y1, B/W1, 
W2

Energize Y1, B/W1, 
W2

Ventilation

Energize A

Energize A

Dehumidification

(if employed)

Energize D

Energize D

Emergency Heat

Energize G, W2, 
W3

Energize G, W2, 
W3

changes. On/Off LAC operation cycles the condenser 
fan on/off to maintain desired liquid pressure while 
modulating LAC operation is factory adjusted and slows 
the condenser fan speed (rpm).

Outdoor Temperature Switch and Freeze Protection 

Thermostat

An outdoor temperature switch and an evaporator 
freeze protection thermostat is supplied with all units 
that have a low ambient control. The outdoor switch 
disables Balanced Climate mode (if enabled) when 
the temperature drops below 50°F. This prevents 
potential evaporator coil freeze up issues. For units 
with mechanical dehumidification, this switch must 
remain disconnected when Balanced Climate mode 
is not being used. Refer to unit wiring diagram. The 
freeze thermostat cuts out compressor operation if the 
evaporator begins to freeze up.

Alarm Relay Feature (Controls Option)

The alarm relay provides a set of NO (normally open) 
and NC (normally closed) pilot duty contacts that 
operate when the compressor control module locks out 
compressor operation because of a high or low system 
refrigerant pressure event.

Dirty Filter Switch Indicator (DFS)

The switch is adjustable and measures pressure drop 
across the unit filter surface. When pressure drop is 
higher than the switch setting, NO contacts are provided 
to indicate the filter needs to be serviced. Refer to page 
35 for instructions on making switch adjustments.

TABLE 3

Low Voltage Connections

Содержание W30HB Series

Страница 1: ...IONS W18HB A W24HB A W24HB B W24HB C W30HB A W30HB B W30HB C W36HB A W36HB B W36HB C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 703H Supersedes 2100 703G Date 3 1 21...

Страница 2: ...tallation 8 Materials Tool List 8 Wall Preparation 8 Wall Mount Installation to Wall Surface 8 Wiring Main Power 15 Wiring Low Voltage 15 Low Voltage Connections 15 Unit Shutdown Feature 15 Balanced C...

Страница 3: ...tallation ANSI NFPA 90A of Air Conditioning and Ventilating Systems Standard for Warm Air ANSI NFPA 90B Heating and Air Conditioning Systems Load Calculation for ACCA Manual J Residential Winter and S...

Страница 4: ...on of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a va...

Страница 5: ...utor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable ins...

Страница 6: ...ensate removal from the outdoor coil when in heating mode The unit must be mounted high enough above grade to ensure that ice will not build up under the unit and come into contact with the base of th...

Страница 7: ...upply duct must be used in the wall cavity to transition between the supply collar on the unit and the supply louver grille in the room The duct must be properly insulated in order to conserve energy...

Страница 8: ...hind the unit that is against the wall A bottom mounting bracket attached to the skid for shipping is provided for ease of installation but is not required Review all requirements listed on unit label...

Страница 9: ...er Access Panel Standard flush vent door for non ERV Econ models 1 Ventilation Air F W 5 88 G All dimensions are in inches Dimensional drawings are not to scale TABLE 1 Clearance Required for Service...

Страница 10: ...NG AT TIME OF INSTALLATION OPENING MIS 3157 A ENTIRE LENGTH OF TOP TOP NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND IS...

Страница 11: ...SHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS DUCT RETURN AIR Right Side View SEAL WI...

Страница 12: ...aintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 of ducting Failure to do so could result in fire causing damage injury or death WARNING SIDE SECTION...

Страница 13: ...NIT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...ed to an external NC normally closed contact such as a fire smoke detector that will cause shutdown of the equipment upon activation Electrical shock hazard Do not operate this equipment without an ea...

Страница 16: ...o control dehumidification operation Ventilation Features Optional See ventilation instructions provided with unit for low voltage wiring Low Ambient Control LAC The low ambient control is a pressure...

Страница 17: ...igent Learning Control BACnet compatible Ethernet compatible 8403 095 T4 Pro 1 stage Cool 2 stage Heat Heat Pump 1 stage Cool 1 stage Heat Conventional Programmable Non Programmable Electronic Auto or...

Страница 18: ...used 6 control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 5 8 and fan set to be programmed fan for the A output to function d...

Страница 19: ...n add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See install manual 4 Factory installed jumper Remove ju...

Страница 20: ...or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control p...

Страница 21: ...dition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur Condenser Fan Operation NOTE Certain models may be equipped with a low ambien...

Страница 22: ...ot gas passing through the outdoor coil melts any accumulated frost When the temperature rises to approximately 57 F the coil temperature sensor will send a signal to the heat pump control which will...

Страница 23: ...nd there is no Y1 at the compressor control module first check to make sure that either the optional vent is plugged into the vent connection plug or the supplied jumper plug is in place The unit will...

Страница 24: ...rol Board 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN...

Страница 25: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 26: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 27: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Страница 28: ...failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The SelecTech...

Страница 29: ...refrigerant charge quantity The pressure tables on the following pages show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informati...

Страница 30: ...150 414 152 440 154 467 156 495 157 524 159 554 161 585 162 618 TABLE 11B Heating Pressure Air Temperature Entering Outdoor Coil F Model Indoor Heating 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 W1...

Страница 31: ...85 72 Low Side High Side 125 302 131 327 136 352 141 377 145 403 148 430 151 458 153 486 154 514 155 543 155 573 155 609 W24HB 75 62 Low Side High Side 116 294 118 314 121 336 123 359 125 382 127 406...

Страница 32: ...14 12 10 These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electrical code latest version Article 310 for power conductor sizing CAUTION...

Страница 33: ...ult W24HB 800 10 700 950 W30HB 1000 15 900 1125 W36HB 1100 15 1000 1200 Rated CFM and ESP on factory speed connection NOTE Be sure to adjust the system static or blower speed to maintain airflows abov...

Страница 34: ...Cooling X X X X Balanced Climate On Full Load Cool X X X X X X Lo Med Hi On Balanced Climate Heat Pump Heating X X X X X Balanced Climate On Full Load Heat Pump Heating X X X X X X X Lo Med Hi On 1st...

Страница 35: ...justment 1 Apply power to the unit 2 Turn the unit indoor blower on energize R G on low voltage terminal board 3 With air filters installed and switch initially set at 0 4 W C see Step 2 under Dirty F...

Страница 36: ...2100 703H Page 36 of 42 FIGURE 17 Adjusting Dirty Filter Switch TURN CLOCKWISE TO INCREASE RESTRICTION AMOUNT REQUIRED TO ACTIVATE THE SWITCH AND COUNTER CLOCKWISE TO DECREASE RESTRICTION AMOUNT MIS...

Страница 37: ...01 793 778 915 898 1040 1014 0 25 777 761 899 878 1017 981 0 30 758 742 880 856 988 944 0 40 716 701 831 806 912 860 0 50 664 655 767 747 814 761 W30HB 0 00 856 823 1083 1063 Dedicated electric heat s...

Страница 38: ...Speed W30H W36H A00 0Z A05 A10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 0Z B05 B09 50 40 30 50 50 35 W30H W36H C00 0Z C05 C09 50 40 30 50 50 40 Models 240V 1 208V 1 240V 3 208V 3 460V 3 KW Amps BTUH...

Страница 39: ...EHW18H A04 X EHW18H A08 X EHW2HB A04 X EHW2HB A08 X EHW2HB B05 X EHW2HB C05 X EHW3HB A05 X EHW3HB A10 X EHW3HB A15 X EHW3HB B05 X EHW3HB B09 X X EHW3HB C05 X X EHW3HB C09 X X EHW30HB A05 X EHW30HB A10...

Страница 40: ...X SK 111 Start Kit Hard Start X X X BOP2 Blank Off Plate X X FAD NE2 Fresh Air Damper No Exhaust X X FAD BE2 Fresh Air Damper Barometric Exhaust X X CRV F2 Commercial Ventilator On Off Spring Return X...

Страница 41: ...Manual 2100 703H Page 41 of 42 GRAPH 1 W18HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 W24HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Страница 42: ...Manual 2100 703H Page 42 of 42 GRAPH 3 W30HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 W36HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Отзывы: