Manual 2100-703H 

Page 

22 of 42

a 2-stage cooling thermostat. This will increase the 
humidity removal up to 35% and provide a much more 
comfortable environment.

NOTE:

  Units with mechanical dehumidification 

require an additional connection to be made 

when enabling Balanced Climate. Refer to 

dehumidification supplemental instructions for 

this step.

 

This mode will also increase the supply temperature 
when in heating mode. When Balanced Climate mode 
is activated it is employed in both heating and cooling 
modes.

If the application is likely to require air conditioning 

operation below 60°F outdoor conditions, a low 

ambient control (LAC) kit must be installed.

 The LAC 

kit is equipped with an outdoor temperature switch 
that disables Balanced Climate mode when the outdoor 
temperature drops below 50°F. This prevents potential 
evaporator coil freeze up issues. The LAC kit also comes 
with an evaporator freeze protection thermostat that cuts 
out the compressor if the evaporator begins to freeze up.

If the unit is being installed with any ventilation 

package, a Bard LAC kit must be installed.

 Failure to 

utilize an LAC with any air conditioner can cause coil 
freeze up.
Balanced Climate can readily be applied to duct-free 
(supply and return air grille) applications. It may also 
be applied to ducted applications with 

limited static 

of 0.20" ESP (total including both supply and return 

statics)

. Consult Bard Application Engineering for 

details prior to implementation.

CAUTION:

 

Balanced Climate is not a replacement for 

a dehumidification (hot gas reheat) unit for extreme 

applications, but rather an enhancement feature for 

limited climates and applications.

Defrost Cycle

The defrost cycle is controlled by temperature and time 
on the solid state heat pump control.
When the outdoor temperature is in the lower 
40°F temperature range or colder, the outdoor coil 
temperature is 32°F or below. This coil temperature is 
sensed by the coil temperature sensor mounted near 
the bottom of the outdoor coil. Once coil temperature 
reaches 30°F or below, the coil temperature sensor 
sends a signal to the control logic of the heat pump 
control and the defrost timer will start accumulating 
run time.
After 30, 60 or 90 minutes of heat pump operation at 
30°F or below, the heat pump control will place the 
system in the defrost mode.
During the defrost mode, the refrigerant cycle switches 
back to the cooling cycle, the outdoor motor stops, 
electric heaters are energized and hot gas passing 
through the outdoor coil melts any accumulated frost. 

When the temperature rises to approximately 57°F, the 
coil temperature sensor will send a signal to the heat 
pump control which will return the system to heating 
operations automatically.
If some abnormal or temporary condition such as a high 
wind causes the heat pump to have a prolonged defrost 
cycle, the heat pump control will restore the system to 
heating operation automatically after 8 minutes.
The heat pump defrost control board has an option of 
30-, 60- or 90-minute setting. By default, this unit 
is shipped from the factory with the defrost time on 
the 60-minute pin. If circumstances require a change 
to another time, remove the wire from the 60-minute 
terminal and reconnect to the desired terminal. Refer 
to Figure 10 on page 24.
There is a cycle speed up jumper on the control. This 
can be used for testing purposes to reduce the time 
between defrost cycle operation without waiting for 
time to elapse.
Use a small screwdriver or other metallic object, or 
another 1/4" QC, to short between the 

SPEEDUP 

terminals to accelerate the HPC timer and initiate 
defrost.
Be careful not to touch any other terminals with the 
instrument used to short the 

SPEEDUP

 terminals. 

It may take up to 10 seconds with the 

SPEEDUP

 

terminals shorted for the speedup to be completed and 
the defrost cycle to start.

As soon as the defrost cycle kicks in, remove the 

shorting instrument from the SPEEDUP terminals.

 

Otherwise the timing will remain accelerated and 
run through the 1-minute minimum defrost length 
sequence in a matter of seconds and will automatically 
terminate the defrost sequence.
There is an initiate defrost jumper (sen jump) on the 
control that can be used at any outdoor ambient during 
the heating cycle to simulate a 0°F coil temperature.
This can be used to check defrost operation of the unit 
without waiting for the outdoor ambient to fall into the 
defrost region.
By placing a jumper across the 

SEN JMP

 terminals (a 

1/4" QC terminal works best) the defrost sensor mounted 
on the outdoor coil is shunted out and will activate 
the timing circuit. This permits the defrost cycle to be 
checked out in warmer weather conditions without the 
outdoor temperature having to fall into the defrost region.
In order to terminate the defrost test, the 

SEN JMP

 

jumper must be removed. If left in place too long, the 
compressor could stop due to the high pressure control 
opening because of high pressure condition created 
by operating in the cooling mode with outdoor fan off. 
Pressure will rise fairly fast as there is likely no actual 
frost on the outdoor coil in this artificial test condition.

Содержание W30HB Series

Страница 1: ...IONS W18HB A W24HB A W24HB B W24HB C W30HB A W30HB B W30HB C W36HB A W36HB B W36HB C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 703H Supersedes 2100 703G Date 3 1 21...

Страница 2: ...tallation 8 Materials Tool List 8 Wall Preparation 8 Wall Mount Installation to Wall Surface 8 Wiring Main Power 15 Wiring Low Voltage 15 Low Voltage Connections 15 Unit Shutdown Feature 15 Balanced C...

Страница 3: ...tallation ANSI NFPA 90A of Air Conditioning and Ventilating Systems Standard for Warm Air ANSI NFPA 90B Heating and Air Conditioning Systems Load Calculation for ACCA Manual J Residential Winter and S...

Страница 4: ...on of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a va...

Страница 5: ...utor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable ins...

Страница 6: ...ensate removal from the outdoor coil when in heating mode The unit must be mounted high enough above grade to ensure that ice will not build up under the unit and come into contact with the base of th...

Страница 7: ...upply duct must be used in the wall cavity to transition between the supply collar on the unit and the supply louver grille in the room The duct must be properly insulated in order to conserve energy...

Страница 8: ...hind the unit that is against the wall A bottom mounting bracket attached to the skid for shipping is provided for ease of installation but is not required Review all requirements listed on unit label...

Страница 9: ...er Access Panel Standard flush vent door for non ERV Econ models 1 Ventilation Air F W 5 88 G All dimensions are in inches Dimensional drawings are not to scale TABLE 1 Clearance Required for Service...

Страница 10: ...NG AT TIME OF INSTALLATION OPENING MIS 3157 A ENTIRE LENGTH OF TOP TOP NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND IS...

Страница 11: ...SHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS DUCT RETURN AIR Right Side View SEAL WI...

Страница 12: ...aintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 of ducting Failure to do so could result in fire causing damage injury or death WARNING SIDE SECTION...

Страница 13: ...NIT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...ed to an external NC normally closed contact such as a fire smoke detector that will cause shutdown of the equipment upon activation Electrical shock hazard Do not operate this equipment without an ea...

Страница 16: ...o control dehumidification operation Ventilation Features Optional See ventilation instructions provided with unit for low voltage wiring Low Ambient Control LAC The low ambient control is a pressure...

Страница 17: ...igent Learning Control BACnet compatible Ethernet compatible 8403 095 T4 Pro 1 stage Cool 2 stage Heat Heat Pump 1 stage Cool 1 stage Heat Conventional Programmable Non Programmable Electronic Auto or...

Страница 18: ...used 6 control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 5 8 and fan set to be programmed fan for the A output to function d...

Страница 19: ...n add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See install manual 4 Factory installed jumper Remove ju...

Страница 20: ...or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control p...

Страница 21: ...dition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur Condenser Fan Operation NOTE Certain models may be equipped with a low ambien...

Страница 22: ...ot gas passing through the outdoor coil melts any accumulated frost When the temperature rises to approximately 57 F the coil temperature sensor will send a signal to the heat pump control which will...

Страница 23: ...nd there is no Y1 at the compressor control module first check to make sure that either the optional vent is plugged into the vent connection plug or the supplied jumper plug is in place The unit will...

Страница 24: ...rol Board 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN...

Страница 25: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 26: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 27: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Страница 28: ...failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The SelecTech...

Страница 29: ...refrigerant charge quantity The pressure tables on the following pages show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informati...

Страница 30: ...150 414 152 440 154 467 156 495 157 524 159 554 161 585 162 618 TABLE 11B Heating Pressure Air Temperature Entering Outdoor Coil F Model Indoor Heating 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 W1...

Страница 31: ...85 72 Low Side High Side 125 302 131 327 136 352 141 377 145 403 148 430 151 458 153 486 154 514 155 543 155 573 155 609 W24HB 75 62 Low Side High Side 116 294 118 314 121 336 123 359 125 382 127 406...

Страница 32: ...14 12 10 These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electrical code latest version Article 310 for power conductor sizing CAUTION...

Страница 33: ...ult W24HB 800 10 700 950 W30HB 1000 15 900 1125 W36HB 1100 15 1000 1200 Rated CFM and ESP on factory speed connection NOTE Be sure to adjust the system static or blower speed to maintain airflows abov...

Страница 34: ...Cooling X X X X Balanced Climate On Full Load Cool X X X X X X Lo Med Hi On Balanced Climate Heat Pump Heating X X X X X Balanced Climate On Full Load Heat Pump Heating X X X X X X X Lo Med Hi On 1st...

Страница 35: ...justment 1 Apply power to the unit 2 Turn the unit indoor blower on energize R G on low voltage terminal board 3 With air filters installed and switch initially set at 0 4 W C see Step 2 under Dirty F...

Страница 36: ...2100 703H Page 36 of 42 FIGURE 17 Adjusting Dirty Filter Switch TURN CLOCKWISE TO INCREASE RESTRICTION AMOUNT REQUIRED TO ACTIVATE THE SWITCH AND COUNTER CLOCKWISE TO DECREASE RESTRICTION AMOUNT MIS...

Страница 37: ...01 793 778 915 898 1040 1014 0 25 777 761 899 878 1017 981 0 30 758 742 880 856 988 944 0 40 716 701 831 806 912 860 0 50 664 655 767 747 814 761 W30HB 0 00 856 823 1083 1063 Dedicated electric heat s...

Страница 38: ...Speed W30H W36H A00 0Z A05 A10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 0Z B05 B09 50 40 30 50 50 35 W30H W36H C00 0Z C05 C09 50 40 30 50 50 40 Models 240V 1 208V 1 240V 3 208V 3 460V 3 KW Amps BTUH...

Страница 39: ...EHW18H A04 X EHW18H A08 X EHW2HB A04 X EHW2HB A08 X EHW2HB B05 X EHW2HB C05 X EHW3HB A05 X EHW3HB A10 X EHW3HB A15 X EHW3HB B05 X EHW3HB B09 X X EHW3HB C05 X X EHW3HB C09 X X EHW30HB A05 X EHW30HB A10...

Страница 40: ...X SK 111 Start Kit Hard Start X X X BOP2 Blank Off Plate X X FAD NE2 Fresh Air Damper No Exhaust X X FAD BE2 Fresh Air Damper Barometric Exhaust X X CRV F2 Commercial Ventilator On Off Spring Return X...

Страница 41: ...Manual 2100 703H Page 41 of 42 GRAPH 1 W18HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 W24HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Страница 42: ...Manual 2100 703H Page 42 of 42 GRAPH 3 W30HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 W36HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Отзывы: