background image

Manual 2100-703H 

Page 

6 of 42

INSTALLATION

Basic Installation Design and 

Application Planning

Successful unit installations require proper planning 
and site inspection before installation begins. Before 
installing the wall mount unit, make sure that all 
service and airflow clearances are met and that the 
unit can meet all applicable code and regulation 
requirements. Provide an inspection of both the inside 
and outside of the structure by reviewing floorplans and/
or visiting the installation site.

Wall Construction

The wall must be inspected to ensure that the weight 
of the unit can be supported. Be sure to review all 
applicable construction codes and regulations including 
seismic requirements. When inspecting wood frame 
walls, the wall construction must be strong and 
rigid enough to carry the weight of the unit without 
transmitting any unit vibration. It is important that 
the side unit wall mounting lags and optional bottom 
bracket are supported by structural members inside 
the wall cavity. Concrete block and brick walls must be 
thoroughly inspected to ensure that they are capable of 
carrying the weight of the installed unit. Metal buildings 
must contain structural components to support the unit 
weight. If heavily corrugated siding is present, it may 
need to be trimmed and flashed to provide a flat, even 
surface to attach and seal the unit to the wall.

Outdoor Area Inspection

Inspect the outdoor area of the jobsite or review 
construction plans and locate the area where the wall 
mount is to be installed. The outdoor area must be 
free from obstructions including fences, bushes and 
walls that will hinder unit operation regarding outdoor 
condenser airflow and unit serviceability. Do not 
install units in enclosed areas that limit the amount 
of ambient temperature airflow. Warm air will exit 
the front condenser section of the unit, and outdoor 
ambient temperature air must be able to enter side 
intake condenser openings of the unit. Portable or 
modular building placement must be in a way that the 
wall mount units have a constant supply of outdoor air 
for proper unit operation. Make sure that the service 
panels of the unit are accessible. Inspect wall surfaces 
for obstructions that could hinder unit installation 
and servicing including outdoor electrical conduits, 
junction boxes, wall drains, vent hoods, windows, doors, 
overhangs and posts.

NOTE: 

Before mounting the heat pump unit, 

consideration should be given to the 

condensate removal from the outdoor coil when 

in heating mode. The unit must be mounted 

high enough above grade to ensure that ice 

will not build up under the unit and come into 

contact with the base of the unit. If allowed, 

this could cause damage to the coil and other 

base components. Also, be sure there are no 

air obstructions to the sides or front of the 

unit, such as bushes or fences, that would 

inhibit condenser airflow.

Condensate Water Drainage

Review all codes and requirements for unit condensate 
drainage. A clear, flexible PVC drain hose (3/4" ID, 1" 
OD) extends from the drain pan in the upper section of 
the unit and extends down to the unit base. An opening 
is supplied towards the back of the unit base for the 
drain hose to pass through, and the hose extends 1" 
to 2" below the unit base. Water removed from the 
indoor air (condensate) will be expelled from the unit 
in large amounts during cooling operation through the 
hose. Units running in cooling operation in cold outdoor 
below freezing conditions can cause the condensate 
to freeze after leaving the drain hose. In the event the 
drain hose is connected to a drain system of some type, 
it must be an open or vented type system to ensure 
proper drainage throughout seasonal use.

Indoor Ducted and Non-Ducted 

Applications

Air distribution inside the structure being conditioned 
plays an important role in making sure the area is 
a consistent temperature. Improper air distribution 
can result in areas being cooler or warmer, electrical 
equipment not receiving sufficient airflow or occupancy 
discomfort felt inside an area. Thermostat or indoor 
temperature sensor placement inside the area being 
conditioned also plays an important role in indoor 
climate control.

Indoor Supply Airflow

Indoor installation areas must provide a non-restrictive 
path for the conditioned supply air to leave supply 
grilles and registers. Inspect the area to ensure that all 
indoor portions of the room or rooms will have access 
to supply air. Ductwork may be used to ensure proper 
air circulation and all provided ductwork guidelines and 
clearances must be followed. Non-ducted applications 
must use a supply louver grille installed over the supply 
opening inside the room. Be sure to adjust supply 
deflectors to properly disperse the conditioned supply 
air to all parts of the room. Avoid closing sections of 
the supply grilles which would cause unneeded supply 
duct pressurization.

Indoor Return Airflow

A non-restrictive path for room air returning to the 
center section of the unit must be provided inside 
the room. Avoid placing objects including furniture, 
electronics equipment, equipment racks and cabinets 

Содержание W30HB Series

Страница 1: ...IONS W18HB A W24HB A W24HB B W24HB C W30HB A W30HB B W30HB C W36HB A W36HB B W36HB C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 703H Supersedes 2100 703G Date 3 1 21...

Страница 2: ...tallation 8 Materials Tool List 8 Wall Preparation 8 Wall Mount Installation to Wall Surface 8 Wiring Main Power 15 Wiring Low Voltage 15 Low Voltage Connections 15 Unit Shutdown Feature 15 Balanced C...

Страница 3: ...tallation ANSI NFPA 90A of Air Conditioning and Ventilating Systems Standard for Warm Air ANSI NFPA 90B Heating and Air Conditioning Systems Load Calculation for ACCA Manual J Residential Winter and S...

Страница 4: ...on of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a va...

Страница 5: ...utor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable ins...

Страница 6: ...ensate removal from the outdoor coil when in heating mode The unit must be mounted high enough above grade to ensure that ice will not build up under the unit and come into contact with the base of th...

Страница 7: ...upply duct must be used in the wall cavity to transition between the supply collar on the unit and the supply louver grille in the room The duct must be properly insulated in order to conserve energy...

Страница 8: ...hind the unit that is against the wall A bottom mounting bracket attached to the skid for shipping is provided for ease of installation but is not required Review all requirements listed on unit label...

Страница 9: ...er Access Panel Standard flush vent door for non ERV Econ models 1 Ventilation Air F W 5 88 G All dimensions are in inches Dimensional drawings are not to scale TABLE 1 Clearance Required for Service...

Страница 10: ...NG AT TIME OF INSTALLATION OPENING MIS 3157 A ENTIRE LENGTH OF TOP TOP NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND IS...

Страница 11: ...SHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS DUCT RETURN AIR Right Side View SEAL WI...

Страница 12: ...aintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 of ducting Failure to do so could result in fire causing damage injury or death WARNING SIDE SECTION...

Страница 13: ...NIT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...ed to an external NC normally closed contact such as a fire smoke detector that will cause shutdown of the equipment upon activation Electrical shock hazard Do not operate this equipment without an ea...

Страница 16: ...o control dehumidification operation Ventilation Features Optional See ventilation instructions provided with unit for low voltage wiring Low Ambient Control LAC The low ambient control is a pressure...

Страница 17: ...igent Learning Control BACnet compatible Ethernet compatible 8403 095 T4 Pro 1 stage Cool 2 stage Heat Heat Pump 1 stage Cool 1 stage Heat Conventional Programmable Non Programmable Electronic Auto or...

Страница 18: ...used 6 control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 5 8 and fan set to be programmed fan for the A output to function d...

Страница 19: ...n add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See install manual 4 Factory installed jumper Remove ju...

Страница 20: ...or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control p...

Страница 21: ...dition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur Condenser Fan Operation NOTE Certain models may be equipped with a low ambien...

Страница 22: ...ot gas passing through the outdoor coil melts any accumulated frost When the temperature rises to approximately 57 F the coil temperature sensor will send a signal to the heat pump control which will...

Страница 23: ...nd there is no Y1 at the compressor control module first check to make sure that either the optional vent is plugged into the vent connection plug or the supplied jumper plug is in place The unit will...

Страница 24: ...rol Board 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN...

Страница 25: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 26: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 27: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Страница 28: ...failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The SelecTech...

Страница 29: ...refrigerant charge quantity The pressure tables on the following pages show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informati...

Страница 30: ...150 414 152 440 154 467 156 495 157 524 159 554 161 585 162 618 TABLE 11B Heating Pressure Air Temperature Entering Outdoor Coil F Model Indoor Heating 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 W1...

Страница 31: ...85 72 Low Side High Side 125 302 131 327 136 352 141 377 145 403 148 430 151 458 153 486 154 514 155 543 155 573 155 609 W24HB 75 62 Low Side High Side 116 294 118 314 121 336 123 359 125 382 127 406...

Страница 32: ...14 12 10 These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electrical code latest version Article 310 for power conductor sizing CAUTION...

Страница 33: ...ult W24HB 800 10 700 950 W30HB 1000 15 900 1125 W36HB 1100 15 1000 1200 Rated CFM and ESP on factory speed connection NOTE Be sure to adjust the system static or blower speed to maintain airflows abov...

Страница 34: ...Cooling X X X X Balanced Climate On Full Load Cool X X X X X X Lo Med Hi On Balanced Climate Heat Pump Heating X X X X X Balanced Climate On Full Load Heat Pump Heating X X X X X X X Lo Med Hi On 1st...

Страница 35: ...justment 1 Apply power to the unit 2 Turn the unit indoor blower on energize R G on low voltage terminal board 3 With air filters installed and switch initially set at 0 4 W C see Step 2 under Dirty F...

Страница 36: ...2100 703H Page 36 of 42 FIGURE 17 Adjusting Dirty Filter Switch TURN CLOCKWISE TO INCREASE RESTRICTION AMOUNT REQUIRED TO ACTIVATE THE SWITCH AND COUNTER CLOCKWISE TO DECREASE RESTRICTION AMOUNT MIS...

Страница 37: ...01 793 778 915 898 1040 1014 0 25 777 761 899 878 1017 981 0 30 758 742 880 856 988 944 0 40 716 701 831 806 912 860 0 50 664 655 767 747 814 761 W30HB 0 00 856 823 1083 1063 Dedicated electric heat s...

Страница 38: ...Speed W30H W36H A00 0Z A05 A10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 0Z B05 B09 50 40 30 50 50 35 W30H W36H C00 0Z C05 C09 50 40 30 50 50 40 Models 240V 1 208V 1 240V 3 208V 3 460V 3 KW Amps BTUH...

Страница 39: ...EHW18H A04 X EHW18H A08 X EHW2HB A04 X EHW2HB A08 X EHW2HB B05 X EHW2HB C05 X EHW3HB A05 X EHW3HB A10 X EHW3HB A15 X EHW3HB B05 X EHW3HB B09 X X EHW3HB C05 X X EHW3HB C09 X X EHW30HB A05 X EHW30HB A10...

Страница 40: ...X SK 111 Start Kit Hard Start X X X BOP2 Blank Off Plate X X FAD NE2 Fresh Air Damper No Exhaust X X FAD BE2 Fresh Air Damper Barometric Exhaust X X CRV F2 Commercial Ventilator On Off Spring Return X...

Страница 41: ...Manual 2100 703H Page 41 of 42 GRAPH 1 W18HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 W24HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Страница 42: ...Manual 2100 703H Page 42 of 42 GRAPH 3 W30HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 W36HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Отзывы: