Blower Status Switch
The unit is equipped with a differential pressure airflow
switch to monitor the blower (see Figure 24). If the
blower is turned on and the switch doesn't close to
indicate there is differential pressure between the inlet
and outlet of the blower, an alarm will be generated.
For switch settings, see Figure 24.
Blower Status Alarm
When the blower is on for 45 seconds and no airflow
is detected by the airflow switch, the compressor
and heating operations will be disabled. The system
will wait 5 minutes before trying again. After three
consecutive no airflow events, the system will generate
an alarm and lockout requiring a user reset.
Filters
The unit is equipped with four (4) 20" x 24" x 2" MERV 8
filters (two per coil). The filters lift and slide into position
making them easy to service. The filters can be serviced
by opening the "hinged" front access panel and locking it
into position. Then lift and slide into position as needed.
Dirty Filter Switch
These units are equipped with a differential pressure
switch to indicate when the filter(s) needs to be
replaced (see Figure 24). The dirty filter switch
measures the pressure difference across the filter
through silicone tubing routed to the blower and
evaporator areas of the unit.
The switch circuit consists of a
normally open
filter
pressure switch. The switch will open when the
pressure differential goes above the setting indicated
on the dial. When the pressure difference returns below
the setting on the dial, the switch will close.
Adjustment of dirty filter switch may be necessary to
ensure proper operation. See Figure 26 to aid in setting
the filter switch to operate at different percentages of
filter blockage.
TABLE 7
Maximum ESP of Operation
Electric Heat Only
* Unit is rated for free blow non-ducted operation with
SG-10W Supply Grille and RG-10W Return Grille.
Model
Static Pressure ("WC)*
-B0Z
-B09
-B18
.50"
.50"
.50"
-C0Z
-C09
-C18
.50"
.50"
.50"
FIGURE 25
Verifying Differential Airflow Status
FIGURE 24
Dirty Filter Switch and Blower Status Switch
Dirty Filter Switch
(W090 Set @ 1.00)
(W120 Set @ 1.40)
(W150 Set @ 1.20)
Blower Status Switch
(W090 Set @ 0.40)
(W120 Set @ 0.80)
(W150 Set @ 0.40)
TABLE 6
Indoor Blower Performance
ESP
(Inch H
2
0)
Dry
Coil
Wet
Coil
W090A
0.25
2980
2850
W120A
0.30
4160
3890
W150A
0.35
4730
4580
Differential airflow status can be viewed by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Digital Inputs
;
press ENTER key.
5. Reference
AIrflw 1
row and
Val
column (see Figure
25).
Содержание MEGA-TEC W090A
Страница 2: ......
Страница 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Страница 60: ...Manual 2100 671C Page 58 of 59...
Страница 61: ...Manual 2100 671C Page 59 of 59...
Страница 62: ......
Страница 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 118: ......
Страница 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Страница 124: ...Manual 2110 1451D Page 6 of 28 SYSTEM COMPONENTS SEXP 898 A 2 15 6 10 14 5 8 13 11 3 7 9 10 1 4 12 16 11...
Страница 126: ...Manual 2110 1451D Page 8 of 28 FAN SYSTEM COMPONENTS 2 5 3 7 2 2 8 4 1 7 9 2 10 5 6 6 9 7 6 12 6 7 11 SEXP 904 7...
Страница 128: ...Manual 2110 1451D Page 10 of 28 SENSORS AND PERIPHERAL DEVICES 7 2 12 10 8 4 4 3 10 12 1 9 7 5 6 11 13 SEXP 905...
Страница 142: ...Manual 2110 1451D Page 24 of 28 INTAKE DAMPER ASSEMBLY SEXP 900 12 17 7 10 13 3 3 6 5 11 4 3 14 8 9 1 15 2 16 18 17...
Страница 144: ...Manual 2110 1451D Page 26 of 28 EXHAUST DAMPER ASSEMBLY 13 17 6 12 16 14 9 5 18 11 4 1 7 2 SEXP 901 7 8 3 1 18 10 15...
Страница 149: ......
Страница 157: ......