PRELIMINARY START UP
FIGURE 13
Cooling and Heating Setpoints
Running in Orphan Mode
With the AC breakers turned on, each MEGA-TEC
wall-mount unit has the capability to run without the
LC6000 controller connected—this feature is called
orphan mode. This keeps the shelter between 60°F and
77°F (factory default settings) by the use of the factory-
installed return air sensor in each wall-mount unit. In
orphan mode, the wall unit uses a continuous blower
setting to circulate room air into the return air inlet and
uses the return air temperature sensor to control room
temperature.
The wall-mount unit can be turned on and off with
the TEC-EYE hand-held diagnostic tool. When ON is
chosen, the wall-mount unit will heat or cool. When set
to OFF using the TEC-EYE, the wall-mount unit will not
heat, cool or ventilate.
To turn the unit on or off with TEC-EYE:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. Press MENU key to go to the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
4. Press UP or DOWN keys to scroll to
On/Off
; press
ENTER key.
5. Press UP or DOWN keys to change value from
ON
to
OFF
or from
OFF
to
ON
.
6. Press ESCAPE key several times to return to Main
Menu screen.
To verify or change the wall-mount unit cooling and
heating setpoints in orphan mode:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints (SET) icon.
Press ENTER key.
3. Press ENTER key to scroll to the selected choice
(see Figure 13).
4. Press UP or DOWN key on desired value until value
displays correctly.
5. Press ENTER key to save and scroll to next
parameter.
6. Press ESCAPE key until Main Menu screen is
displayed.
During installation, the ability to run in orphan mode
allows deactivation of one of the existing, older wall-
mount units, while keeping the shelter cool with the
other unit still operating. Once the first of the Bard
MEGA-TEC wall-mount units is installed, orphan mode
can be enabled early in the installation—keeping the
climate inside the shelter stable and the installers
comfortable while the remainder of the older equipment
is removed and the remaining Bard MEGA-TEC wall-
mount units and LC6000 controller are installed.
Additionally, should any or all of the MEGA-TEC wall-
mount units lose communication with the LC6000
controller (such as during maintenance), they will
continue to serve the shelter’s needs until a repair can
be made.
NOTE:
Screenshots shown in this manual reflect
default settings (when applicable).
Содержание MEGA-TEC W090A
Страница 2: ......
Страница 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Страница 60: ...Manual 2100 671C Page 58 of 59...
Страница 61: ...Manual 2100 671C Page 59 of 59...
Страница 62: ......
Страница 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 118: ......
Страница 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Страница 124: ...Manual 2110 1451D Page 6 of 28 SYSTEM COMPONENTS SEXP 898 A 2 15 6 10 14 5 8 13 11 3 7 9 10 1 4 12 16 11...
Страница 126: ...Manual 2110 1451D Page 8 of 28 FAN SYSTEM COMPONENTS 2 5 3 7 2 2 8 4 1 7 9 2 10 5 6 6 9 7 6 12 6 7 11 SEXP 904 7...
Страница 128: ...Manual 2110 1451D Page 10 of 28 SENSORS AND PERIPHERAL DEVICES 7 2 12 10 8 4 4 3 10 12 1 9 7 5 6 11 13 SEXP 905...
Страница 142: ...Manual 2110 1451D Page 24 of 28 INTAKE DAMPER ASSEMBLY SEXP 900 12 17 7 10 13 3 3 6 5 11 4 3 14 8 9 1 15 2 16 18 17...
Страница 144: ...Manual 2110 1451D Page 26 of 28 EXHAUST DAMPER ASSEMBLY 13 17 6 12 16 14 9 5 18 11 4 1 7 2 SEXP 901 7 8 3 1 18 10 15...
Страница 149: ......
Страница 157: ......