Manual 2100-671C
Page
31 of 59
chosen:
Dry Bulb
(Figure 43),
TempHum
(Figure
44) or
Enthalpy
(Figure 45). The following menu
shows the
Enthalpy
content which also contains
parameters that would be shown on
Dry Bulb
(temperature only) and
TempHum
(temperature
and humidity only).
18. Press ENTER key to scroll to
OA Temp Set
(on
Drybulb Control
and
Temp/Hum Control A3
screens, this parameter will be titled
Outdoor Set
).
19. Press UP or DOWN keys to change the temperature
setpoint to desired value.
20. Press ENTER key to save the value and scroll to
Off Diff
.
21. Press UP or DOWN keys to adjust the outdoor
temperature differential for which the economizer
is re-enabled.
22. Press ENTER key to save the value and scroll to
OA
Hum Set
.
23. Press UP or DOWN keys to adjust the humidity
setpoint to desired value.
24. Press ENTER key to save the value and scroll to
On
Diff
.
25. Press UP or DOWN keys to adjust the outdoor
humidity differential for which the economizer is
re-enabled.
26. Press ENTER key to save the value and scroll to
Dew Pt. Set
.
27. Press UP or DOWN keys to adjust the outdoor dew
point setpoint for economizer operation to the
desired value.
28. Press ENTER key to save the value and scroll to
On
Diff
.
29. Press UP or DOWN keys to adjust the dew point
differential for which the economizer is re-enabled.
30. Press ENTER key to save the value.
31. Press ESCAPE key several times to return to Main
Menu screen.
See Table 10 for default settings for economizer
operation.
FIGURE 45
Economizer Setup – Enthalpy Control
FIGURE 44
Economizer Setup – Temp/Hum Control
FIGURE 43
Economizer Setup – Dry Bulb Control
TABLE 10
Economizer Default Settings
* In Enthalpy mode, outdoor temperature, humidity and calculated dew point are all considered for economizer operation.
Mode
Consideration
Economizer Available for Cooling
Economizer Not Available for Cooling
Temp
Only
Temp &
Humidity
Enthalpy*
Temperature
When the outdoor air temperature
is below 70°F
When the outdoor air temperature
is above 75°F
Humidity
When the outdoor humidity is below
80%
When the outdoor humidity is above
80%
Dew Point
When the outdoor dew point
is below 55°F
When the outdoor dew point
is above 60°F
Содержание MEGA-TEC W090A
Страница 2: ......
Страница 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Страница 60: ...Manual 2100 671C Page 58 of 59...
Страница 61: ...Manual 2100 671C Page 59 of 59...
Страница 62: ......
Страница 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 118: ......
Страница 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Страница 124: ...Manual 2110 1451D Page 6 of 28 SYSTEM COMPONENTS SEXP 898 A 2 15 6 10 14 5 8 13 11 3 7 9 10 1 4 12 16 11...
Страница 126: ...Manual 2110 1451D Page 8 of 28 FAN SYSTEM COMPONENTS 2 5 3 7 2 2 8 4 1 7 9 2 10 5 6 6 9 7 6 12 6 7 11 SEXP 904 7...
Страница 128: ...Manual 2110 1451D Page 10 of 28 SENSORS AND PERIPHERAL DEVICES 7 2 12 10 8 4 4 3 10 12 1 9 7 5 6 11 13 SEXP 905...
Страница 142: ...Manual 2110 1451D Page 24 of 28 INTAKE DAMPER ASSEMBLY SEXP 900 12 17 7 10 13 3 3 6 5 11 4 3 14 8 9 1 15 2 16 18 17...
Страница 144: ...Manual 2110 1451D Page 26 of 28 EXHAUST DAMPER ASSEMBLY 13 17 6 12 16 14 9 5 18 11 4 1 7 2 SEXP 901 7 8 3 1 18 10 15...
Страница 149: ......
Страница 157: ......