Manual 2100-705B
Page
15 of 43
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310
for power conductor sizing.
CAUTION:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310
regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a raceway.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance
with the National Electrical Code and all local codes.
Model
Rated Volts
& Phase
No. Field
Power
Circuits
Single Circuit
Dual Circuit
Minimum
Circuit
Ampacity
Maximum
External Fuse
or Ckt. Brkr.
Field Power
Wire Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
W090APB0Z
B09
B18
230/208-
60-3
1
1
1
46
46
59
60
60
60
6
6
6
10
10
10
W090APC0Z
C09
C18
460-60-3
1
1
1
26
26
26
40
40
40
8
8
8
10
10
10
W120APB0Z
B09
B18
230/208-
60-3
1 or 2
1 or 2
1 or 2
56
56
59
70
70
70
6
6
6
8
8
8
32
32
32
25
28
28
40
40
40
40
40
40
8
8
8
8
8
8
10
10
10
10
10
10
W120APC0Z
C09
C18
460-60-3
1
1
1
27
27
30
40
40
40
8
8
8
10
10
10
W120APE0Z
E09
E18
220/200-
50-3
1
1
1
55
55
59
70
70
70
6
6
6
8
8
8
W120APV0Z
V07
V14
415-50-3
1
1
1
27
27
30
40
40
40
8
8
8
10
10
10
W120APQ0Z
Q09
Q18
575-60-3
1
1
1
24
24
27
35
35
35
8
8
8
10
10
10
W150APB0Z
B09
B18
230/208-
60-3
1 or 2
1 or 2
1 or 2
67
67
67
80
80
80
4
4
4
8
8
8
39
39
39
29
29
29
50
50
50
40
40
40
8
8
8
8
8
8
10
10
10
10
10
10
W150APC0Z
C09
C18
460-60-3
1
1
1
32
32
32
40
40
40
8
8
8
10
10
10
TABLE 2A
Electrical Specifications – W***AP Series
Model
Rated Volts
& Phase
No. Field
Power
Circuits
Single Circuit
Dual Circuit
Minimum
Circuit
Ampacity
Maximum
External Fuse
or Ckt. Brkr.
Field Power
Wire Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
W120AEB09
B18
230/208-
60-3
1 or 2
1 or 2
83
110
90
120
4
2
8
6
59
59
25
55
60
60
30
30
6
6
10
6
10
10
10
10
W120AEC09
C18
460-60-3
1
1
40
54
50
60
8
6
10
10
W120AEE07
E14
220/200-
50-3
1 or 2
1 or 2
82
110
90
120
4
2
8
6
59
59
24
46
60
60
40
60
6
6
8
8
10
10
10
10
W120AEV07
V14
415-50-3
1
1
40
53
50
60
8
6
10
10
W120AEQ09
Q18
575-60-3
1
1
32
43
40
45
8
8
10
10
TABLE 2B
Electrical Specifications – W***AE Series
Содержание MEGA-TEC W090A
Страница 2: ......
Страница 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Страница 60: ...Manual 2100 671C Page 58 of 59...
Страница 61: ...Manual 2100 671C Page 59 of 59...
Страница 62: ......
Страница 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 118: ......
Страница 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Страница 124: ...Manual 2110 1451D Page 6 of 28 SYSTEM COMPONENTS SEXP 898 A 2 15 6 10 14 5 8 13 11 3 7 9 10 1 4 12 16 11...
Страница 126: ...Manual 2110 1451D Page 8 of 28 FAN SYSTEM COMPONENTS 2 5 3 7 2 2 8 4 1 7 9 2 10 5 6 6 9 7 6 12 6 7 11 SEXP 904 7...
Страница 128: ...Manual 2110 1451D Page 10 of 28 SENSORS AND PERIPHERAL DEVICES 7 2 12 10 8 4 4 3 10 12 1 9 7 5 6 11 13 SEXP 905...
Страница 142: ...Manual 2110 1451D Page 24 of 28 INTAKE DAMPER ASSEMBLY SEXP 900 12 17 7 10 13 3 3 6 5 11 4 3 14 8 9 1 15 2 16 18 17...
Страница 144: ...Manual 2110 1451D Page 26 of 28 EXHAUST DAMPER ASSEMBLY 13 17 6 12 16 14 9 5 18 11 4 1 7 2 SEXP 901 7 8 3 1 18 10 15...
Страница 149: ......
Страница 157: ......