Manual 2100-671C
Page
18 of 59
To put the blower into override:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Fans / Blowers
;
press ENTER key.
5. Press UP or DOWN keys to scroll to
Blower 1
.
6. Press ENTER key to scroll to Blower
Overrides
?
(see Figure 23).
7. Press UP or DOWN key to change
No
to
Go
. The
override will begin and the screen will change to
the override screen (see Figure 23).
The override will last for 5 minutes or until the
Blower
Overrides
parameter is set to
No
again.
EEV Operation
EEV Superheat Control
The electronic expansion valve (EEV) will open or
close to maintain the superheat setpoint while the
compressor is running (see Table 4). When the
compressor is not running, the valve will close to the
20% open default position.
FIGURE 22
Adjusting Evaporator Freeze Sensor Values
FIGURE 23
Putting Blower Output into Override Mode
TABLE 5
Rated Airflow
Nominal Rated CFM
Nominal Rated ESP
High
Low
W090A
3000
2100
0.25
W120A
4000
2800
0.30
W150A
4600
2800
0.35
TABLE 4
Unit Specific Superheat Setpoints
Unit
Superheat
W090A
14°F
W120A
10°F
W150A
14°F
Low superheat protection will be active once the
superheat value is at or below 5°F. At this point,
the control will aggressively close the valve so that
superheat is maintained.
Additional EEV Alarms
Low Superheat Alarm
This alarm will become active when the calculated
superheat goes below 5°F. This alarm will clear itself
when the condition is no longer present.
This alarm cannot be adjusted.
Indoor Airflow
Indoor Airflow Components
Blower
The unit is equipped with a blower that is driven by an
electronically commutated motor (ECM). The blower
is controlled by a 0-100% signal through Modbus
communication. The motor controller converts this
signal to a PWM signal. The blower uses a 22" (560
mm) diameter wheel and operates up to 1500 rpm.
The blower output can be put into an override mode for
verification or troubleshooting.
Содержание MEGA-TEC W090A
Страница 2: ......
Страница 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Страница 60: ...Manual 2100 671C Page 58 of 59...
Страница 61: ...Manual 2100 671C Page 59 of 59...
Страница 62: ......
Страница 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 118: ......
Страница 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Страница 124: ...Manual 2110 1451D Page 6 of 28 SYSTEM COMPONENTS SEXP 898 A 2 15 6 10 14 5 8 13 11 3 7 9 10 1 4 12 16 11...
Страница 126: ...Manual 2110 1451D Page 8 of 28 FAN SYSTEM COMPONENTS 2 5 3 7 2 2 8 4 1 7 9 2 10 5 6 6 9 7 6 12 6 7 11 SEXP 904 7...
Страница 128: ...Manual 2110 1451D Page 10 of 28 SENSORS AND PERIPHERAL DEVICES 7 2 12 10 8 4 4 3 10 12 1 9 7 5 6 11 13 SEXP 905...
Страница 142: ...Manual 2110 1451D Page 24 of 28 INTAKE DAMPER ASSEMBLY SEXP 900 12 17 7 10 13 3 3 6 5 11 4 3 14 8 9 1 15 2 16 18 17...
Страница 144: ...Manual 2110 1451D Page 26 of 28 EXHAUST DAMPER ASSEMBLY 13 17 6 12 16 14 9 5 18 11 4 1 7 2 SEXP 901 7 8 3 1 18 10 15...
Страница 149: ......
Страница 157: ......