Manual 2100-705B
Page
40 of 43
Menu Screens and Password Levels
MEGA-TEC Wall-Mount Units
A
System Config: User (2000)
B
Adv Sys Config: Technician (1313)
C
I-O Config: Technician (1313)
D
On/Off: User (2000)
E
Alarm Logs: User (2000)
F
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Serial Ports: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart: User (2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
G
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
LC6000 Controller
A
System Config
General: User (2000)
Zone 1: User (2000)
Zone 2: User (2000)
Zone 3: User (2000)
B
Adv Sys Config: B1-B13 Technician (1313)
C
I-O Config: C1-C10 Technician (1313)
D
On/Off: User (2000)
E
Alarm Logs: User (2000)
F
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Serial Ports: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart: User (2000)
ADDITIONAL INFORMATION
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
G
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
Setpoints
The
LC6000
setpoints will determine the cooling and
heating setpoints when
communicating with the wall-
mount units
. The
unit
cooling and heating setpoints
will determine the cooling and heating setpoints when
in orphan mode
. It is important to note that once the
wall-mount unit establishes communication with the
LC6000, the setpoints from the LC will override the
wall-mount unit setpoints. If a unit returns to orphan
mode after communicating with LC, it will operate with
last communicated setpoints from the LC.
If at any time the unit(s) loses communication with
the LC6000 controller, the unit(s) will go into orphan
mode.
Calibrating Sensors
1. Press MENU key on LC controller interface to go to
the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to sensor to be
adjusted.
5. Press ENTER key to scroll to
Offset
(see Figure
48).
6. Press UP or DOWN keys to add or subtract to the
sensor offset value.
7. Press ENTER key to save.
FIGURE 48
Adjusting Sensor Offset Value
Содержание MEGA-TEC W090A
Страница 2: ......
Страница 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Страница 60: ...Manual 2100 671C Page 58 of 59...
Страница 61: ...Manual 2100 671C Page 59 of 59...
Страница 62: ......
Страница 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 118: ......
Страница 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Страница 124: ...Manual 2110 1451D Page 6 of 28 SYSTEM COMPONENTS SEXP 898 A 2 15 6 10 14 5 8 13 11 3 7 9 10 1 4 12 16 11...
Страница 126: ...Manual 2110 1451D Page 8 of 28 FAN SYSTEM COMPONENTS 2 5 3 7 2 2 8 4 1 7 9 2 10 5 6 6 9 7 6 12 6 7 11 SEXP 904 7...
Страница 128: ...Manual 2110 1451D Page 10 of 28 SENSORS AND PERIPHERAL DEVICES 7 2 12 10 8 4 4 3 10 12 1 9 7 5 6 11 13 SEXP 905...
Страница 142: ...Manual 2110 1451D Page 24 of 28 INTAKE DAMPER ASSEMBLY SEXP 900 12 17 7 10 13 3 3 6 5 11 4 3 14 8 9 1 15 2 16 18 17...
Страница 144: ...Manual 2110 1451D Page 26 of 28 EXHAUST DAMPER ASSEMBLY 13 17 6 12 16 14 9 5 18 11 4 1 7 2 SEXP 901 7 8 3 1 18 10 15...
Страница 149: ......
Страница 157: ......