FIGURE 25
Communication Wiring: Termination at the First Wall-Mount Unit
1. From the controller, extend the shielded cable through a separate conduit
and route to the provided terminal block next to the wall-mount control
board.
These connections are polarity-sensitive. Two-wire communication from
control board is prewired to terminal block. Make sure to match "+" and "-"
symbols on controller terminal block.
2. Connect the wires matching the terminal
designations (+/-) of the controller
terminals. Leave the drain wire loose.
3. Connect another cable in a similar
fashion (“daisy chain”) to route in
conduit to the second wall-mount unit.
Connect both drain wires with wire nut.
From LV1000
Controller
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 1 Terminal Block
From LV1000
Controller
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 1 Terminal Block
To Wall-Mount Unit 2
From LV1000
Controller
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 1 Terminal Block
Wall-Mount Unit 1
–
+
–
+
–
+